Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: DP16-0012
Parcel: 10706002K

Review Status: Active

Review Details: SITE and/or GRADING

Permit Number - DP16-0012
Review Name: SITE and/or GRADING
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2016 Any LANDSCAPE REVIEW Active
01/20/2016 ANY NPPO REVIEW Active
01/21/2016 STEVE SHIELDS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: 902 W. Miracle Mile - Expansion
Development Package (1st Review)
DP16-0012

TRANSMITTAL DATE: January 21, 2016

DUE DATE: Walk-Thru

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

The review comments include the actual standard first with the applicable Administrative Manual section number and the following paragraph is the actual comment related to the specific item that must be addressed. If you need to review the sections listed below click on the link or copy it in the address bar of your internet program. http://www.amlegal.com/nxt/gateway.dll/Arizona/tucson_az_udc/administrativemanual?f=templates$fn=default.htm$3.0$vid=amlegal:tucson_udc_az

This link will take you directly to the section used for the standards review. The UDC & TSM requirements are in the Unified Development Code and can be viewed at the same web link as above

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is January 19, 2017.

SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS)
Section

2-06.1.0 GENERAL

2-06.2.0 APPLICATION SUBMITTAL REQUIREMENTS

2-06.3.0 FORMAT REQUIREMENTS

2-06.4.0 CONTENT REQUIREMENTS

2-06.5.0 FLEXIBLE LOT DEVELOPMENT (FLD) - ADDITIONAL REQUIREMENTS

2-06.1.0 GENERAL

2-06.1.1 PURPOSE
This standard has been prepared for the purpose of informing applicants of the submittal and review requirements for development package documents to assure proper and adequate information is presented in a consistent manner, thereby providing the basis for an efficient and timely review. The development package documents are prepared in support of applications for building permits and related reviews.

The information that is requested establishes the basis upon which the project will be approved and could affect what is required of the property in the future, should there be a proposal for expansion or for a different use of the property.

This standard does not waive any applicable city regulations or codes.

2-06.1.2 APPICABILITY
This standard shall be used for all site plans and tentative plats submitted to PDSD for review.

2-06.2.1 APPLICATION SUBMITTAL REQUIREMENTS
Development Package applications are available from PDSD. Completed applications and accompanying materials shall be submitted to PDSD. Incomplete or inaccurate applications will not be accepted, nor will any application in which the pre-application conference or neighborhood meeting requirements have not been met. The types of documents and the specific number of copies required of each of the documents are on the PDSD website or may be obtained from PDSD. Resubmittals of development packages require a comment response letter that details how all previous comments have been addressed. Provide the same number of copies of the comment response letter as plans provided.
The following documents and information shall be submitted upon application:

2-06.2.1 Application Form
A completed application signed by the property owner or authorized designee;

2-06.2.2 Development Package
A development package must be prepared to the format and content requirements described herein;

2-06.2.3 Related Reviews
In addition to the plan process, a project may require review for other types of plans and documents. The applications for those processes are submitted to the appropriate department for review and approval. These related reviews can be applied for so that review can occur concurrently with the development package application. However, it must be understood that, should the related application be approved subject to conditions or denied, this may affect the;

2-06.2.4 Concurrent Reviews
The development package is designed to allow for concurrent review of any site related reviews. Concurrent review means that all plans and documents needed for the review are submitted as one package. Examples of site related reviews include but are not limited to: site plans, landscape plans, NPPO plans, water harvesting plans, grading plans, SWPPP plans, floodplain use permits, and overlay reviews. Separate applications are often required for the different site related reviews even if the plans are submitted concurrently; and,

2-06.2.5 Fees
Fees in accordance with Section 4-01.0.0, Development Review Fee Schedule.

2-06.3.0 FORMAT REQUIREMENTS

2-06.3.5 - A three-inch by five-inch space shall be reserved in the lower right quadrant of each sheet for an approval stamp.

1. COMMENT: Provide the PDSD Development Package approval stamp in the lower right quadrant of all sheets. The required stamp can be found at http://pdsd.tucsonaz.gov/pdsd/development-permits under Development Package.

CONTENT REQUIREMENTS

2-06.4.3 - The administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet.

2. COMMENT: Provide the development package case number, DP16-0012, adjacent to the title block on each sheet.

2-06.4.4 - The project-location map to be located on the first sheet of the development package in the upper right corner, shall cover approximately one square mile, be drawn at a minimum scale of three inch equals one mile, and provide the following information.

3. COMMENT: Provide a location map on the development package 1st sheet the meets the requirements above and below.

2-06.4.2.A - Show the subject property approximately centered within the one square mile area;

4. COMMENT: Provide the above information.

2-06.4.2.B - Identify major streets and regional watercourses within the square mile area and all streets that abut the subject property; and,

5. COMMENT: Provide the above information.

2-06.4.2.C - Section, township, and range; section corners; north arrow; and the scale will be labeled.

6. COMMENT: Provide the above information.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes

2-06.4.7.A.1 - List as a general note: "Existing zoning is ____."

7. COMMENT: Provide a general note stating "EXISTING ZONING IS C-2"

2-06.4.7.A.2 - List the gross area of the site/subdivision by square footage and acreage.

8. COMMENT: Provide a general note listing the gross are of the site by square footage and acreage.


2-06.4.7.A.4 - Identify the existing and proposed use of the property as classified per the UDC. List all UDC sections applicable to the proposed uses.

9. COMMENT: Provide a general note stating "THE EXISTING USE IS GENERAL MERCHANDISE SALES, PROPOSED USE GENERAL MERCHANDISE SALES, EXCLUDING LARGE RETAIL ESTABLISHMENT, SUBJECT TO USE SPECIFIC STANDARD 4.9.9.B.1".

2-06.4.8 - Existing Site Conditions
The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided.

2-06.4.8.A - Provide site boundary/subdivision perimeter information, including bearing in degrees, minutes, and seconds, with basis for bearing noted, together with distances in feet, to hundredths of a foot, or other functional reference system.

10. COMMENT: Provide the site boundary information, including bearing in degrees, minutes, and seconds, together with distances in feet

2-06.4.8.C - The following information regarding existing private or public right-of-way adjacent to or within the site shall be provided: the name, right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts, and sidewalks.

11. COMMENT: Provide the above right-of-way info on the plan.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

2-06.4.9.F - All existing zoning classifications on and adjacent to the project (including across any adjacent right-of-way) shall be indicated on the drawing with zoning boundaries clearly defined. If the property is being rezoned, use those boundaries and classifications. The basis for this requirement is that some zoning requirements on a project are based on the zoning classification of adjacent property. Also, in some instances, each zone has to be taken into consideration on property that is split by two or more zoning classifications, as each may have different requirements.

12. COMMENT: Provide the above information on the plan.

2-06.4.9.H.5.a - Show all motor vehicle off-street parking spaces provided fully dimensioned. As a note, provide calculations on the number of spaces required (include the ratio used) and the number provided, including the number of spaces required and provided for the physically disabled. The drawing should indicate parking space locations for the physically disabled. A typical parking space detail shall be provided for both standard parking spaces and those for the physically disabled. For information on parking requirements for the physically disabled, refer to adopted building and accessibility codes of the City of Tucson. Design criteria for parking spaces and access are located in Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC.

13. COMMENT: Provide a wheel spot location dimension for the proposed wheel stops shown on the plan. See UDC Article 7.4.6.H.3.

14. COMMENT: Zoning recommends that the wheel stops shown for the two (2) southern most vehicle parking spaces be removed as they are not a requirement and may cause a safety issue in the future.

2-06.4.9.H.5.d - Show bicycle parking facilities fully dimensioned. For specifics, refer to Section 7.4.9, Bicycle Parking Design Criteria, of the UDC. Provide, as a note, calculations for short and long term bicycle spaces required and provided.

15. COMMENT: Provide a short and long term bicycle parking space calculation on the plan. This calculation should address the number required and number provide. See UDC Table 7.4.8-1.

16. COMMENT: Provide a short and long term bicycle detail. The detail for the short term bicycle parking should address UDC Articles 7.4.9.B & .C, the detail for the long term bicycle parking should address UDC Articles 7.4.9.B & .D.

2-06.4.9.Q - Provide the square footage and the height of each commercial, industrial, or business structure and the specific use proposed within the footprint of the building(s).

17. COMMENT: Provide the height of the building, existing and addition, within the footprint of the building.

2-06.4.9.R - Show on-site pedestrian circulation and refuge utilizing location and the design criteria in Section 7-01.0.0, Pedestrian Access, of the Technical Standards Manual.

18. COMMENT: Per TSM Section 7-01.4.1.A At least one sidewalk is required to a project from each street on which the project has frontage, unless there is no vehicular access from a street because of a physical barrier, such as a drainageway or an unbroken security barrier (e.g., a wall or fence). The sidewalk should be located to minimize any conflict with vehicular access to the project. That said provide a 4'-0" wide sidewalk from the proposed addition to the sidewalk within the right-of-way along Miracle Mile and to the property line along Fairview.

19. COMMENT: Per TSM Section 7-01.4.1.B A sidewalk is required adjacent and parallel to any access lane or PAAL on the side where buildings are located. That said provide a 4'-0" sidewalk along the north, south and west side of the proposed addition.

20. COMMENT: Demonstrate on the plan that the sidewalk shown between the proposed and/or existing accessible ramp meets the minimum sidewalk width of 4'-0", see TSM Section 7-01.4.3.A.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
01/21/2016 SSHIELD1 H/C SITE REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: 902 W. Miracle Mile - Expansion
Accessibility Review - On Site Only
Development Package (1st Review)
DP16-0012

TRANSMITTAL DATE: January 20, 2016

DUE DATE: Walk-Thru

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. Per IBC 1104.1 demonstrate on the plan that there is an accessible route to one of the right-of-ways that meets the requirements of IBC Chapter 11 and the ICC A117.1-2009.

2. Provide a note on the plan stating that all accessible route slopes are to comply with ICC A117.1, Section 403.3; 5% maximum running slopes and 2% maximum cross slopes.

3. Provide a large scale detail of the accessible parking space showing all accessible requirements such as dimensions, markings, grade slopes, accessible parking aisle, signage, van accessible space and access to the accessible route. Per the 2012 IBC, Table 1106.1, the accessible vehicle parking space is required to be a van accessible parking space. Demonstrate on the detail that the accessible space meets the requirements of ICC A117.1, Section 502.2.

4. Provide a large scale sign detail including a van accessible sign.

5. Provide a detail for the proposed and/or existing accessible ramp shown on the plan that demonstrates how the requirements of IBC Chapter 11 and ICC A117.1-2009 are met.
01/21/2016 SSHIELD1 ADA REVIEW Passed
02/08/2016 LOREN MAKUS ENGINEERING REVIEW Reqs Change Show dimensions of driveway openings.
Distance from property line to bollards around propane tank.
Show drainage patterns including roof drainage. Ensure that roof drainage is not directed over the sidewalk.
02/09/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Revise the site drawing to include the location, invert and rim elevations of the upstream manhole, along with the Pima County Wastewater Management Department (PCWMD) reference number. If the rim elevation of the next upstream sanitary manhole is higher than the first floor elevation or is less than 12" below the first floor elevation, provide a note on the plans requiring the installation of a backwater valve when future plumbing activities take place. Reference: Section 715.1, IPC 2012, as amended by the City of Tucson.
02/09/2016 MARTIN BROWN FIRE REVIEW Approved