Permit Review Detail
Review Status: Completed
Review Details: DEV PKG - RESUBMITTAL
Permit Number - DP15-0204
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/14/2016 | FERNE RODRIGUEZ | START | PLANS SUBMITTED | Completed | |
| 01/25/2016 | TIM ROWE | PIMA COUNTY | WASTEWATER | Reqs Change | NOTE: Type error in comment below: DP15-0204 correct Permit. *********************** Michael, Attached is the wastewater review letter for the following project: TMC Medical Services Facilities @ Civano Development Plan (DP15-0294)– 2nd Submittal P15WS00048 Respectfully, Tom Thomas W.Porter, P.E. Civil Engineer Pima County Regional Wastewater Reclamation Dept Development Liaison Unit 201 N. Stone Ave., 1st Floor, Tucson, AZ 85701-1207 ph: (520) 724-6719 Pima County Regional Wastewater Reclamation Department Jackson Jenkins Director 201 N. Stone Ave., 8th Floor Tucson, Arizona 85701-1207 PH: (520) 740-6500 FAX: (520) 620-0135 January 22, 2016 To: Michael J. Baker, P.E. Baker & Associates Engineering, Inc. Thru: Patricia Gehlen City of Tucson Development Services ____________________________________ From: Erica Sanchez, CEA, PCRWRD (520) 724-6934 Subject: TMC Medical Services Facilities @ Civano Development Plan (DP15-0294)- 2nd Submittal P15WS00048 The Pima County Regional Wastewater Reclamation Department (PCRWRD) has reviewed the proposed sewer design for the above-referenced project. The Pima County Regional Wastewater Reclamation Department has found the following deficiencies in the above referenced submittal of the Preliminary Sewer Layout (PSL), based upon PCRWRD Engineering Design Standards (EDS) 2012. 1. Sheet 3: The invert elevations shown for the proposed public manholes do not match with the proposed slopes. Please revise. 2. Sheet 3: Consider proposed BCS connection tap directly to manhole or change the proposed size of pipe to 4". This office will require a revised set of plans, and a response letter, addressing these comments. Additional comments may be made during the review of these documents. All comments cited in this letter are based upon PCRWRD Engineering Design Standards 2012 and PCRWRD Standard Specifications and Details for Construction 2012. Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the Preliminary Sewer Layout. The fee for the first submittal is $166 plus $50 per Sheet. For the second submittal, the review fee is $50.00 per sheet. For all subsequent submittals, the review fee is $39 per sheet. The next plan submittal will require a review fee of $39.00 made payable to Pima County Treasurer. If you have any questions regarding this matter please contact me at your convenience. Cc. Lorenzo Hernandez, P.E., RWRD Francisco Galindo, P.E., RWRD Erica Sanchez, CEA, RWRD Project file P15WS00048 |
| 01/28/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 02/02/2016 | MARTIN BROWN | COT NON-DSD | FIRE | Approved | . |
| 02/05/2016 | ANDREW CONNOR | LANDSCAPE | REVIEW | Approved | . |
| 02/08/2016 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 02/08/2016 | PGEHLEN1 | COT NON-DSD | ENVIRONMENTAL SERVICES | Approved | Patricia, The City of Tucson - Environmental Services Department (ES) has completed our second review of the Development Package Application materials for the proposed TMC Medical Services Facilities at Civano. Mr. Ken Perry completed the initial review of this development package on behalf of ES. The three review comments from the initial review and the response prepared by Baker & Associates Engineering, Inc. for this proposed site are as follows: 1. Change the note in Detail 4 on Sheet 3 to state the enclosure will be constructed in accordance with Figures 2 and 3A in TSM Sections 8-01 and 9.0. Correct the notes and dimensions on this Detail drawing. Response: The note in Detail 4 on Sheet 3 was properly added and the notes and dimensions were properly modified. 2. Include waste stream calculations next to Detail 4 on Sheet 3. Response: The waste stream calculations were properly prepared in accordance with TSM Section 8-01.8.0. The waste stream calculations require that 4 cubic yards of waste storage capacity is needed at the proposed TMC Medical Services facility. 3. There appears to be a grade shown on the enclosure on Sheet 5 that does not allow drainage to flow away from the enclosure and apron. The enclosure floor and apron are to slope at a minimum of 2 percent away from the enclosure per the notes in Figure 3A. Response: The enclosure floor and apron have a slope of 2 percent away from the enclosure, in accordance with the notes in Figure 3A in the TSM. Based on this review, the Development Package Application materials for the proposed TMC Medical Services Facilities at Civano relating to solid waste storage and collection are approved. Please let me know if there are any questions regarding this approval. Thank you. Thomas G. Ryan, P.E. Environmental Services Department |
| 02/09/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approv-Cond | Per conversation with the designer, an overflow pipe is needed to drain basin to adjacent drainage ditch invert to compensate for the infiltration test not including a derating factor. |
| 02/10/2016 | PATRICIA GEHLEN | ZONING-DECISION LETTER | REVIEW | Reqs Change | Per discussion with Baker and Associates. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/10/2016 | PGEHLEN1 | APPROVAL SHELF | Completed |
| 02/10/2016 | PGEHLEN1 | OUT TO CUSTOMER | Completed |
| 02/10/2016 | PGEHLEN1 | REJECT SHELF | Completed |