Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: DP15-0173
Parcel: 141220280

Address:
9255 S RITA RD

Review Status: Completed

Review Details: RESUB - SITE and/or GRADING

Permit Number - DP15-0173
Review Name: RESUB - SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/03/2016 STEVE SHIELDS ZONING REVIEW Approved
02/05/2016 ANDREW CONNOR NPPO REVIEW Approved
02/05/2016 ELIZABETH LEIBOLD ENGINEERING REVIEW Approved