Permit Number: DP15-0102
Parcel: 305972280

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - DP15-0102
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/13/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change It appears that lots 161, 237, and 247 are more than 12" above the rim elevation of the next upstream manhole and shall not have a backwater valve. Conversely, lots 228 and 296 respectively are less than 12" above or lower than the next upstream manhole will require the installation of backwater valves. [Second Comment: Comment not resolved. Provide the FFE for each lot.] [Initial Comment: Raising the elevations of the roads 1-foot and re-grading the lots may affect the need for backwater valves. Provide the site utility drawings showing the proposed sewer system including the manhole rim elevations, sewer connection points and the FFE for each lot. Reference: Section 107.2.1, IBC 2012.]
12/15/2021 SBEASLE1 ZONING-DECISION LETTER WRITE DECISION LETTER Reqs Change Email from: COTDSDPermits
To: Linda Thompson
Wed 12/15/2021 11:43 AM

REVISION REVIEW NOTICE
Returned for corrections, DP15-0102

DESCRIPTION: GRADING/SWPPP - The Vistas at Rincon Knolls, Phase 2, Lots 161 thru 349, Block 1, and Common Areas "A", ":B", C", "E" (no "D"). 10495 S MILLICENT TR

FEE BALANCE: $0 (zero) Thank you for the payment

VIEW the review comments and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on View to the right of each document

YOUR NEXT STEPS: Submit documents to the Filedrop
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
Select "Existing Application"

1) Comment Response Letter (your response to
the reviewer's Requires changes comments)
2) Plan Set (or individual sheets)
3) Any other items/documents requested by review staff

Thank you.
Sharon Beasley, Building Permit Specialist

City of Tucson, Planning and Development Services
Email: COTDSDpermits@TucsonAz.gov
(disregard the email response that will be sent automatically)