Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: DP15-0102
Parcel: 305972280

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - DP15-0102
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/29/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Raising the elevations of the roads 1-foot and re-grading the lots may affect the need for backwater valves. Provide the site utility drawings showing the proposed sewer system including the manhole rim elevations, sewer connection points and the FFE for each lot. Reference: Section 107.2.1, IBC 2012.
08/02/2021 STEVE SHIELDS ZONING REVIEW Approved
08/31/2021 SBLOOD1 ENGINEERING REVIEW Reqs Change 1. Clearly show the effect of raising the roads 1.0' along the NUOS Limits. The line work on the plans doesn't seem to show any difference, raising the grade 1.0' will either steepen the daylighting grade or push out the limits of disturbance. Neither seem to be reflected on the plans.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
09/01/2021 SBEASLE1 ZONING-DECISION LETTER WRITE DECISION LETTER Reqs Change Email from: COTDSDPermits
To: Linda Thompson
Wed 9/1/2021 10:29 AM

Revision Returned for Corrections: DP15-0102

DESCRIPTION: GRADING/SWPPP - THE VISTAS AT RINCON KNOLLS, phase 2, Lots 161-349 and Common Areas "A" through "E". 10495 S MILLICENT TR

Fee Balance: $0 (zero) Thank you for the payment.

INCLUDE IN YOUR RESUBMITTAL
1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set pages
3) Any other documents requested by review staff

FILEDROP
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
(Select "Existing Application", then enter permit number)

SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab and you will see different sections
- Reviews section - click on REVIEW DETAILS
- Documents section - click on VIEW


Thank you.
Sharon Beasley, Permit Specialist

City of Tucson, Planning and Development Services
Email for Development Pkgs: COTDSDpermits@TucsonAz.gov
(disregard the email response that will be sent automatically)
Email for Building Permits: PDSDinquiries@TucsonAz.gov