| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/29/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Raising the elevations of the roads 1-foot and re-grading the lots may affect the need for backwater valves. Provide the site utility drawings showing the proposed sewer system including the manhole rim elevations, sewer connection points and the FFE for each lot. Reference: Section 107.2.1, IBC 2012. |
| 08/02/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 08/31/2021 | SBLOOD1 | ENGINEERING | REVIEW | Reqs Change | 1. Clearly show the effect of raising the roads 1.0' along the NUOS Limits. The line work on the plans doesn't seem to show any difference, raising the grade 1.0' will either steepen the daylighting grade or push out the limits of disturbance. Neither seem to be reflected on the plans. Stephen Blood (520) 837-4958 Stephen.blood@tucsonaz.gov |
| 09/01/2021 | SBEASLE1 | ZONING-DECISION LETTER | WRITE DECISION LETTER | Reqs Change | Email from: COTDSDPermits To: Linda Thompson Wed 9/1/2021 10:29 AM Revision Returned for Corrections: DP15-0102 DESCRIPTION: GRADING/SWPPP - THE VISTAS AT RINCON KNOLLS, phase 2, Lots 161-349 and Common Areas "A" through "E". 10495 S MILLICENT TR Fee Balance: $0 (zero) Thank you for the payment. INCLUDE IN YOUR RESUBMITTAL 1) Comment Response Letter (your response to the reviewer's Requires Change comments) 2) Plan Set pages 3) Any other documents requested by review staff FILEDROP https://docs.tucsonaz.gov/Forms/tucsonpermitapp (Select "Existing Application", then enter permit number) SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro (If information is not available, check back later after data transfers to PRO.) - Home page, Activity Search, enter the Activity/Permit Number - Permits - click on blue tab and you will see different sections - Reviews section - click on REVIEW DETAILS - Documents section - click on VIEW Thank you. Sharon Beasley, Permit Specialist City of Tucson, Planning and Development Services Email for Development Pkgs: COTDSDpermits@TucsonAz.gov (disregard the email response that will be sent automatically) Email for Building Permits: PDSDinquiries@TucsonAz.gov |