Permit Number: DP15-0054
Parcel: 10704002G

Address:
1485 W GLENN ST

Review Status: Completed

Review Details: RESUB - SITE/GRADING ALL

Permit Number - DP15-0054
Review Name: RESUB - SITE/GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/05/2016 MARTIN BROWN FIRE REVIEW Approved
04/12/2016 SSHIELD1 H/C SITE REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
Principle Planner

PROJECT: Mobile Mini
Development Package (2nd Review)
DP15-0054

TRANSMITTAL DATE: April 12, 2016

DUE DATE: April 21, 2016

COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. This comment was not addressed. There is nothing on the plan or detail that shows that the allowed running and cross slopes are not exceeded. Provide an accessible route from the public right of way to the accessible parking spaces and to all building entrances on the site.
a. Insure accessible route slopes comply with the 2009 ICC A117.1, Section 403.3.

2. This comment was not addressed. There is nothing on the plan or detail that shows that the allowed running and cross slopes are not exceeded. Provide a large scale detail of the accessible parking space including all accessible requirements such as dimensioning, van accessible space, grades, markings, signage, access to and the accessible route.

3. Provide a mounting height dimension on detail 2 sheet 8. The dimension should be 7'-0" from the bottom of sign to grade.

4. Detail 1 sheet 8 provide a sidewalk width dimension from the propose accessible sign west to the edge of sidewalk that demonstrates that the minimum 4'-0" sidewalk width is maintained.

5. Remove the detectable warnings from all on-site ramps as they are only required at passenger transit platforms and curb ramps in the public right-of-way per IBC Section 1109.10.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov
04/12/2016 STEVE SHIELDS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: Mobile Mini
Development Package (2nd Review)
DP15-0054

TRANSMITTAL DATE: April 12, 2016

DUE DATE: April 21, 2016

COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

The review comments include the actual standard first with the applicable Administrative Manual section number and the following paragraph is the actual comment related to the specific item that must be addressed. If you need to review the sections listed below click on the link or copy it in the address bar of your internet program. http://www.amlegal.com/nxt/gateway.dll/Arizona/tucson_az_udc/administrativemanual?f=templates$fn=default.htm$3.0$vid=amlegal:tucson_udc_az

This link will take you directly to the section used for the standards review. The UDC & TSM requirements are in the Unified Development Code and can be viewed at the same web link as above

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is March 25, 2016.

SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS)
Section

2-06.1.0 GENERAL

2-06.2.0 APPLICATION SUBMITTAL REQUIREMENTS

2-06.3.0 FORMAT REQUIREMENTS

2-06.4.0 CONTENT REQUIREMENTS

2-06.5.0 FLEXIBLE LOT DEVELOPMENT (FLD) - ADDITIONAL REQUIREMENTS

2-06.1.0 GENERAL

2-06.1.1 PURPOSE
This standard has been prepared for the purpose of informing applicants of the submittal and review requirements for development package documents to assure proper and adequate information is presented in a consistent manner, thereby providing the basis for an efficient and timely review. The development package documents are prepared in support of applications for building permits and related reviews.

The information that is requested establishes the basis upon which the project will be approved and could affect what is required of the property in the future, should there be a proposal for expansion or for a different use of the property.

This standard does not waive any applicable city regulations or codes.

2-06.1.2 APPICABILITY
This standard shall be used for all site plans and tentative plats submitted to PDSD for review.

2-06.2.1 APPLICATION SUBMITTAL REQUIREMENTS
Development Package applications are available from PDSD. Completed applications and accompanying materials shall be submitted to PDSD. Incomplete or inaccurate applications will not be accepted, nor will any application in which the pre-application conference or neighborhood meeting requirements have not been met. The types of documents and the specific number of copies required of each of the documents are on the PDSD website or may be obtained from PDSD. Resubmittals of development packages require a comment response letter that details how all previous comments have been addressed. Provide the same number of copies of the comment response letter as plans provided.
The following documents and information shall be submitted upon application:

2-06.2.1 Application Form
A completed application signed by the property owner or authorized designee;

2-06.2.2 Development Package
A development package must be prepared to the format and content requirements described herein;

2-06.2.3 Related Reviews
In addition to the plan process, a project may require review for other types of plans and documents. The applications for those processes are submitted to the appropriate department for review and approval. These related reviews can be applied for so that review can occur concurrently with the development package application. However, it must be understood that, should the related application be approved subject to conditions or denied, this may affect the;

2-06.2.4 Concurrent Reviews
The development package is designed to allow for concurrent review of any site related reviews. Concurrent review means that all plans and documents needed for the review are submitted as one package. Examples of site related reviews include but are not limited to: site plans, landscape plans, NPPO plans, water harvesting plans, grading plans, SWPPP plans, floodplain use permits, and overlay reviews. Separate applications are often required for the different site related reviews even if the plans are submitted concurrently; and,

2-06.2.5 Fees
Fees in accordance with Section 4-01.0.0, Development Review Fee Schedule.

2-06.3.0 FORMAT REQUIREMENTS

2-06.3.1 - Each sheet shall measure 24 inches by 36 inches and include a minimum one inch margin on left side and one-half inch margin on all other sides to facilitate efficient record keeping. A larger sheet format may be used with the approval of the Planning and Development Services Department (PDSD).

1) Addressed. COMMENT:

2-06.3.2 - All mapped data shall be drawn at an engineering scale having no more than 50 feet to the inch. This scale is the minimum accepted to assure the plan will be legible during review and when digitized and/or reduced for record-keeping purposes. The same scale shall be used for all sheets within the set. Smaller scales (60:1 or greater) may be used for some or all of the sheets with the prior approval of PDSD when it is determined legibility and the ability to be digitized and/or reduced for archiving will not be affected.

2) Addressed. COMMENT: Revise the plans to meet this standard.

2-06.3.12 - An index of sheets in the development package shall be provided on the first sheet.

3) COMMENT: Remove the Individual Parking Plan (IPP) from this development package as it is a separate submittal.

CONTENT REQUIREMENTS

2-06.4.2 - The title block shall include the following information and be provided on each sheet:

2-06.4.2.D - The page number and the total number of pages in the package (i.e., sheet xx of xx).

4) Addressed. COMMENT: The total number sheets will change as the IPP is to be removed.

2-06.4.3 - The administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet.

5) Addressed. COMMENT: Remove the address from the title block and provided it adjacent to the title block on each sheet.

6) Addressed. COMMENT: Provide the development package case number, DP15-0054, adjacent to the title block on each sheet.

7) Addressed. COMMENT: Once approved provide the IPP case number adjacent to the title block on each sheet.

2-06.4.4 - The project-location map to be located on the first sheet of the development package in the upper right corner, shall cover approximately one square mile, be drawn at a minimum scale of three inch equals one mile, and provide the following information.

2-06.4.2.B - Identify major streets and regional watercourses within the square mile area and all streets that abut the subject property; and,

8) Addressed. COMMENT: Identify the Santa Cruz river on the location map.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A.6.a - List additional applications and overlays, by case number (if applicable), in lower right corner of each sheet. As a general note provide the type of application processed or overlays applicable, a statement that the project meets the criteria/conditions of the additional application or overlay, the case number, date of approval, what was approved, and the conditions of approval, if any.

9) COMMENT: If approved provide a general note stating the IPP case number, date of approval, what was approved and if applicable in conditions of approval.

2-06.4.7.A.8 - For development package documents provide:

2-06.4.7.A.8.a - Floor area for each building;

10) Addressed. COMMENT: As a general note provide the floor are for each building.

2-06.4.8 - Existing Site Conditions
The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided.

2-06.4.8.A - Provide site boundary/subdivision perimeter information, including bearing in degrees, minutes, and seconds, with basis for bearing noted, together with distances in feet, to hundredths of a foot, or other functional reference system.

11) This comment was not addressed. COMMENT: As this site is made up of two parcels a lot combination or a recorded Covenant Regarding Development and Use of Real is required. Provide a copy of the approved Pima Country Combo Request form or the recorded Covenant Regarding Development and Use of Real with the next submittal.

12) Addressed. COMMENT: Remove the reference to Headlee Roofing and the lot reconfiguration from the plan as this process has been completed.

2-06.4.8.B - All easements shall be drawn on the plan. The recordation information, location, width, and purpose of all easements on site will be stated. Blanket easements should be listed in the notes, together with recordation data and their proposed status. Should an easement not be in use and be proposed for vacation or have been abandoned, so indicate. However, should the easement be in conflict with any proposed building location, vacation of the easement shall occur prior to approval of plan unless written permission from easement holder(s) is provided.

13) Addressed. COMMENT: Provide the recordation information for all existing easements shown on the plan.

2-06.4.8.C - The following information regarding existing private or public right-of-way adjacent to or within the site shall be provided: the name, right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts, and sidewalks.

14) Addressed. COMMENT: Provide the dimensioned width of paving, curbs, and curb cuts for the Glenn right-of-way (ROW).

15) Addressed. COMMENT: Sheet 2 shows Glenn Street as an "MSR STREET". This section of Glenn is not shown on the COT MS&R maps.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

2-06.4.9.H.2 - Show future and existing sight visibility triangles (SVTs). On a designated MS&R street, the sight visibility triangles are based on the MS&R cross-section.

16) Addressed. COMMENT: If applicable show the required SVTs on the plan.

2-06.4.9.H.5 - If utilizing parking area access lanes (PAALs), they shall be designed in accordance with Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC.

17) Addressed. COMMENT: Provide a fully dimensioned vehicle use area.

18) This comment was not addressed. The process to modify the type of surfacing for a vehicle use area is not a TSMR, see UDC Article 7.4.6.I.c. COMMENT: It does not appear that the vehicle use area that accesses the 'EMPLOYEE PARKING SPACES" meets the requirements of UDC Article 7.4.6.I

19) Addressed. COMMENT: Per UDC Article 7.4.6.H Barriers, such as post barricades or wheel stop curbing, are required in a vehicular use area to prevent vehicles from extending beyond the property lines, to prevent cars from damaging adjacent landscaping, walls, or buildings, overhanging adjacent sidewalk areas, and/or driving onto unimproved portions of the site. That said some type of barrier is required between the PAAL and the landscape area along the north side of the site.

2-06.4.9.H.5.a - Show all motor vehicle off-street parking spaces provided, fully dimensioned. As a note, provide calculations on the number of spaces required (include the ratio used) and the number provided, including the number of spaces required and provided for the physically disabled. The drawing should indicate parking space locations for the physically disabled. A typical parking space detail shall be provided for both standard parking spaces and those for the physically disabled. For information on parking requirements for the physically disabled, refer to adopted building and accessibility codes of the City of Tucson. Design criteria for parking spaces and access are located in Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC.

20) Addressed. COMMENT: Show all motor vehicle off-street parking spaces provided, fully dimensioned.

21) Zoning acknowledges that an IPP has been applied for. Until the IPP is approved Zoning cannot approve the development package. COMMENT: As a note, provide calculations on the number of spaces required (include the ratio used) and the number provided, including the number of spaces required and provided for the physically disabled. Zoning acknowledges that a vehicle parking calculation was provided on sheet 4 but as this sheet will not be part of the development package provide a calculation on the cover sheet. If does not appear that the building area shown on the vehicle parking calculation on sheet 4 includes the total gross floor area on the site.

22) Addressed. COMMENT: A typical parking space detail shall be provided for both standard parking spaces and those for the physically disabled.

23) This comment was not addressed. The process to modify the type of surfacing for a vehicle use area is not a TSMR, see UDC Article 7.4.6.I.c. COMMENT: It does not appear that the 'EMPLOYEE PARKING SPACES" meet the requirements of UDC Article 7.4.6.I

2-06.4.9.H.5.d - Show bicycle parking facilities fully dimensioned. For specifics, refer to Section 7.4.9, Bicycle Parking Design Criteria, of the UDC. Provide, as a note, calculations for short and long term bicycle spaces required and provided.

24) Addressed. COMMENT: Provide a short and long term bicycle parking space calculation that shows the required and provided number. Zoning acknowledges that a vehicle parking calculation was provided on sheet 4 but as this sheet will not be part of the development package provide a calculation on the cover sheet. Also it appears that In-Lieu fees are proposed instead of providing the required number of long term bicycle parking spaces. That said it does not appear that this site qualifies for In-Lieu fees, see UDC Article 7.4.8.B.1.a.(2) The in-lieu fee may not be used if there are vehicular use areas, plazas, exterior courtyards, or other open areas on the site, other than required landscaping, large enough, separately or in combination, to accommodate all or a portion of the required bicycle parking.

25) Addressed. COMMENT: Provide a long term bicycle parking detail that shows how the requirements of UDC Article 7.4.9.D are met.

2-06.4.9.O - All applicable building setback lines, such as erosion hazard, floodplain detention/retention basins, and zoning, including sight visibility triangles, will be shown.

26) Based on the height provided of 19'-0" the required street perimeter yard setback would be 28'-6" See UDC Article 6.4.5.C.1. Based on the 21'-8" street perimeter yard setback dimension shown on the plan a Design Development Option (DDO) is required. COMMENT: Show the required street perimeter yard setbacks from the proposed structure to the street property line, see UDC Article 6.4.5.C.1.

2-06.4.9.R - Show on-site pedestrian circulation and refuge utilizing location and the design criteria in Section 7-01.0.0, Pedestrian Access, of the Technical Standards Manual.

27) As there are no existing sidewalks within the right-of-way (ROW) and no sidewalks are proposed within the ROW the required sidewalk to the street only needs to run to the property line. COMMENT: Per TSM 7-01.4.1.A At least one sidewalk is required to a project from each street on which the project has frontage, unless there is no vehicular access from a street because of a physical barrier, such as a drainageway or an unbroken security barrier (e.g., a wall or fence). The sidewalk should be located to minimize any conflict with vehicular access to the project. That said provide a sidewalk/pedestrian path from the structures on site to the ROW.

28) Addressed. COMMENT: Per TSM 7-01.4.1.B A sidewalk is required adjacent and parallel to any access lane or PAAL on the side where buildings are located. That said provide a sidewalk along the north side of the covered work area, restrooms, office, east side of the offices, west side of the restrooms.

29) Addressed. COMMENT: Per TSM 7-01.4.1.C A sidewalk is required adjacent to any parking space accessed by a PAAL where the space is located on the same side of the PAAL as any building and no other parking spaces or PAALs intervene. That said provide a sidewalk along the south side of the office.

Addressed. See red line for sidewalk requirements.

2-06.4.9.T - Show refuse collection areas, including locations of dumpsters, screening location and materials, and vehicle maneuverability, fully dimensioned, and access route. If dumpster service is not proposed, indicate type of service. For specific information on refuse collection, refer to Section 8-01.0.0, Solid Waste and Recycle Disposal, Collection, and Storage, of the Technical Standards Manual. Refuse collection on all projects shall be designed based on that section, even if collection is to be contracted to a private firm.

30) Addressed. COMMENT: Show the refuse collection area on the plan.

2-06.4.9.W - Indicate the locations and types of proposed signs (wall, free-standing, pedestal) to assure there are no conflicts with other requirements and that minimal locational requirements can be met. Indicate if there are any existing billboards on site. Compliance to the Sign Code, Chapter 3 of the Tucson Code, is required.

31) Addressed. COMMENT: If applicable show the location of any existing or proposed signs on the plan.

32) Addressed. COMMENT: Provide a general note on the plan "ALL SIGNAGE TO BE UNDER SEPARATE PERMIT".

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package, Approved Pima Country Combo Request form.
04/15/2016 LOREN MAKUS ENGINEERING REVIEW Needs Review There are no continuing comments. However, once the IPP has been approved, Engineering will review for conditions of approval of the IPP as related to engineering.
04/21/2016 JOE LINVILLE LANDSCAPE REVIEW Approved
04/22/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed