Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: DP15-0052
Parcel: 14041128A

Review Status: Completed

Review Details: RESUB - SITE and/or GRADING

Permit Number - DP15-0052
Review Name: RESUB - SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/01/2015 LOREN MAKUS ENGINEERING REVIEW Approved
05/01/2015 ANDREW CONNOR NPPO REVIEW Approved
05/01/2015 DAVID RIVERA ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/12/2015 CPIERCE1 APPROVAL SHELF Completed