Permit Review Detail
Review Status: Completed
Review Details: TENTATIVE PLAT REVIEW
Permit Number - DP15-0039
Review Name: TENTATIVE PLAT REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/08/2015 | KROBLES1 | START | PLANS SUBMITTED | Completed | |
| 05/19/2015 | ED ABRIGO | PIMA COUNTY | ASSESSOR | Approved | Office of the Pima County Assessor 115 N. Church Ave. Tucson, Arizona 85701 BILL STAPLES ASSESSOR TO: CDRC Office Subdivision Review City of Tucson (FAX# 791-5559) FROM: Ada Griffin GIS Cartographer Pima County Assessor's Office DATE: May 19, 2015 RE: Assessor's Review and Comments Regarding: DP15-0039 - SHOPS F TUCSON MARKETPLACE - PAD 15 _ * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * X Plat meets Assessor's Office requirements for a Development Package. _______ Plat does not meet Assessor's Office requirements. COMMENTS: Thank you for your submittal. NOTE: THE ASSESSOR'S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED. |
| 05/28/2015 | STEVE SHIELDS | ZONING | REVIEW | Approv-Cond | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Steve Shields Lead Planner PROJECT: Shops "F" Tucson Market Place Development Package (2nd Review) DP15-0039 TRANSMITTAL DATE: May 22, 2015 DUE DATE: June 8, 2015 The Zoning Review Section conditionally approves the development package for this project subject to the following. 2-06.4.7.A - Zoning and Land Use Notes 2-06.4.7.A.7 - If the property is part of a subdivision plat that is being reviewed or has been recorded, provide the case number in the lower right corner of each sheet. As a general note, indicate whether the project is part of a Flexible Lot Development (FLD), condominium, or another similar type project. 2-06.4.9 - Information on Proposed Development The following information on the proposed project shall be shown on the drawing or added as notes. 2-06.4.9.H.5.d - Show bicycle parking facilities fully dimensioned. For specifics, refer to Section 7.4.9, Bicycle Parking Design Criteria, of the UDC. Provide, as a note, calculations for short and long term bicycle spaces required and provided. 1. This comment was not fully addressed. Detail 3/G-1 shows 30' from the post not the edge of the loop to the building wall and the minimum distance between racks should be 4'-0" not 30". COMMENT: Detail 3/G-1 does not meet the requirement UDC Articles 7.4.9.B.2.f, & .g and UDC Figure 7.4.9-C. If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package |
| 05/28/2015 | JANE DUARTE | COT NON-DSD | PARKS & RECREATION | Approved | Tucson Parks and Recreation has no further comments or concerns. Howard B. Dutt, RLA Landscape Architect Tucson Parks & Recreation (520) 837-8040 Howard.Dutt@tucsonaz.gov >>> DSD_CDRC 5/11/2015 9:54 AM >>> Dear Reviewers: PLEASE SEE THE RESPONSE LETTER FOR OWNER DRIVEN CHANGES. This is an electronic distribution for a CDRC Tentative Plat/Development Package review. If you normally receive paper copies of the review documents, you will receive them soon. The applicable case numbers are: CDRC Development Plan: DP15-0039 Existing and Proposed Zoning: PAD-15 |
| 05/29/2015 | ELIZABETH LEIBOLD | ENGINEERING | REVIEW | Approv-Cond | DATE: May 22, 2015 TO: Jeff Behrana P.E. Optimus Engineering SUBJECT: Development Package Engineering Re-plat Block 6 / Development Plan 2nd Review submittal PROJECT: Tucson Market Place Shops F Development Package LOCATION: 1500 E TUCSON MARKETPLACE BL, Ward 5 FEMA PANEL: 2237K, Zone X-Unshaded WATERSHED: Mission View Wash Watershed adjacent to Greyhound Wash Detention Area REVIEWER: Elizabeth Leibold P.E. ACTIVITY NUMBER: DP15-0039 SUMMARY: The Development Package that includes the Development Plan, Grading Plan, SWPP, & Tentative Plat for re-platting Block 6 for the Tucson Market Place Shops F was received and reviewed by Planning & Development Services Department Engineering Division for the 2nd submittal. Development Services Department Engineering Division recommends approval of this Development Package with the following consideration as a suggestion. TENTATIVE PLAT CONSIDERATIONS: 1) Consider adding to legend the lot labeling on sheet TP-2 to differentiate between old lot numbering and new lots 1-9 - perhaps using darker/bolder font type. Please be aware, standard grading permit conditions shall apply including providing as-built prior to final inspection. If you have questions, call me at 837-4934. Elizabeth Leibold, P.E., CPM, CFM Civil Engineer Engineering Division Planning & Development Services Dept |
| 05/29/2015 | PGEHLEN1 | PIMA COUNTY | ADDRESSING | Approved | 201 N. STONE AV, 1ST FL TUCSON, AZ 85701-1207 MICHELENE NOWAKADDRESSING REVIEW PH #: 721-9512 TO: CITY PLANNING FROM: MICHELENE NOWAK, ADDRESSING REVIEW SUBJECT: DP15-0039/TENTATIVE PLAT SHOPS F-TUCSON MARKETPLACE 2ND REVIEW DATE: May 28, 2015 The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project. 1.) Submit a 24 x 36 Reverse Reading Double Matte Photo Mylar of approved Final Plat to City Planning ***PIMA COUNTY ADDRESSING MUST RECEIVE A COPY OF THE RECORDED FINAL PLAT PRIOR TO THE ASSIGNMENT OF ANY ADDRESSES. PLEASE COORDINATE THE DELIVERY AND RECORDATION OF THE MYLAR WITH THE CITY OF TUCSON PLANNING*** 2.) All addresses will need to be displayed per Pima County Address Standards at the time of final inspection. ***The Pima County Addressing Section can use digital CAD drawing files. These CAD files can be e-mailed to: CADsubmittals@pima.gov The digital CAD drawing files expedite the addressing and permitting processes when we are able to insert this digital data into the County’s Geographic Information System. Your support is greatly appreciated.*** |
| 06/02/2015 | ANDREW CONNOR | LANDSCAPE | REVIEW | Approv-Cond | Identification and Descriptive Data All improvements and site information, such as adjacent rights-of-way and property lines, shown on the grading plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the grading plan which will then be resubmitted along with the base plan. Ensure that all Zoning and Engineering comments and concerns are addressed. |
| 06/03/2015 | SSHIELD1 | H/C SITE | REVIEW | Reqs Change | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Steve Shields Lead Planner PROJECT: Shops "F" Tucson Market Place - Accessibility Review Development Package DP15-0039 TRANSMITTAL DATE: June 3, 2015 Following discussions with Chris Kiel, Building Official, per IBC Section 1109.10 detectable warnings are required only at transportation platforms and should be removed from all locations on this development. If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov |
| 06/05/2015 | LIZA CASTILLO | UTILITIES | TUCSON ELECTRIC POWER | Approved | See map in PRO 4350 E. Irvington Road, Tucson, AZ 85714 Post Office Box 711, Tucson, AZ 85702 WR#292950 June 4, 2015 Optimus Civil Design Group Attn: Jeff Behrana, P.E. 4650 E. Cotton Ctr. Suite 200 Phoeniz, Arizona 85040 Dear Jeff: SUBJECT: Shops F Tucson MarketPlace DP15-0039 Tucson Electric Power Company has reviewed and approved the development plan submitted May 11, 2015. It appears that there are no conflicts with the existing facilities within the boundaries of this proposed development. Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities. Any relocation costs will be billable to the customer. In order to apply for electric service, call the New Construction Department at (520) 918-8300. Submit a final set of plans including approved site, electrical load, paving off-site improvements and irrigation plans, if available include a CD with the AutoCAD version of the plans. If easements are required, they will be secured by separate instrument. Your final plans should be sent to: Tucson Electric Power Company Attn: Mr. Richard Harrington New Business Project Manager P. O. Box 711 (DB-101) Tucson, AZ 85702 520-917-8726 Should you have any technical questions, please call the area Designer Jennifer Necas (520) 918-8295. Sincerely, Patty Lopez Administrative Assistant Design Enclosures CC: J. Necas - TEP City of Tucson |
| 06/08/2015 | PGEHLEN1 | ENV SVCS | REVIEW | Approved | The Development Package has been reviewed on behalf of the Environmental Services Dept. and is approved. If there are any questions, I can be reached at kperry@perryengineering.net |
| 06/08/2015 | PATRICIA GEHLEN | ZONING-DECISION LETTER | REVIEW | Reqs Change | Two rolled sets of the plans required |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/08/2015 | PGEHLEN1 | APPROVAL SHELF | Completed |
| 06/08/2015 | PGEHLEN1 | OUT TO CUSTOMER | Completed |
| 06/08/2015 | PGEHLEN1 | REJECT SHELF | Completed |