Permit Number: DP14-0246
Parcel: 141186350

Review Status: Completed

Review Details: GRADING

Permit Number - DP14-0246
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2015 DAVID RIVERA ZONING REVIEW Reqs Change Project: DP14-0246


Zoning has reviewed the grading plan but cannot approve at this time until the engineering and landscape reviewers have approved the grading plan.
01/23/2015 ANDREW CONNOR NPPO REVIEW Reqs Change Ensure that all Engineering comments and concerns are addressed.

Additional comments may apply
01/26/2015 LOREN MAKUS ENGINEERING REVIEW Denied Provide documentation of permission for the off-site grading and off-site drainage solution.
Show erosion prevention measures for the new proposed channel. Show expected velocity and appropriate surface treatment.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/03/2015 CPIERCE1 OUT TO CUSTOMER Completed