Permit Number: DP14-0242
Parcel: 140420320

Address:
6920 S TUCSON BL

Review Status: Completed

Review Details: SITE and/or GRADING

Permit Number - DP14-0242
Review Name: SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2015 MARTIN BROWN FIRE REVIEW Approved
01/14/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Revise the site drawing to include the following information:
a. The location of sanitary and storm sewers, including the pipe diameter and the invert and rim elevations of all manholes and cleanouts; along with the Pima County Wastewater Management Department (PCWMD) reference number.
b. The points of connection to existing public sewers.
c. Any existing or proposed utility easements
d. If an on-site sewage disposal system is or is to be located on site, show the location of all individual components for the disposal system, including any reserve areas and indicate the required separation distances.
Reference: City of Tucson Administrative Manual No. 2-06.0.0, Section 4.8 and Section 107.2.13, IBC 2012.
01/14/2015 ANDREW CONNOR NPPO REVIEW Approved
01/14/2015 ANDREW CONNOR LANDSCAPE REVIEW Approved
01/23/2015 RONALD BROWN H/C SITE REVIEW Approved Need to provide Accessible parking spaces
01/23/2015 RBROWN1 ADA REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
03/04/2015 SHANAE POWELL OUT TO CUSTOMER Completed