Permit Review Detail
Review Status: Completed
Review Details: RESUB - SITE/GRADING ALL
Permit Number - DP14-0241
Review Name: RESUB - SITE/GRADING ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/24/2015 | JASON GREEN | ENGINEERING | REVIEW | Reqs Change | DATE: June 25, 2015 DUE DATE: July 16, 2015 SUBJECT: Rialto Development Plan Package- 2nd Engineering Review TO: Perry Engineering; Attn: Ken Perry, PE LOCATION: 211 E Broadway Blvd REVIEWERS: Jason Green, CFM ACTIVITY: DP14-0241 SUMMARY: Engineering Division of Planning & Development Services Department has received and reviewed the proposed Development Package. Engineering Division does not recommend approval of the Development Package at this time. This review falls under the Unified Development Code (UDC), Administration Manual (AM) and Technical Standards Manual (TSM). Refer to the links for further clarification: http://www.amlegal.com/nxt/gateway.dll/Arizona/tucson_az_udc/administrativemanual?f=templates$fn=default.htm$3.0$vid=amlegal:tucson_udc_az The following items need to be addressed: SITE PLAN: 1) Restated: AM Sec.2-06.4.3: The relevant Development Package case number (DP14-0241) may be added to the lower right hand corner of the plan on all sheets. Sheets 4 and 5 must include the DP Case Number also. 2) Complied. 3) Complied. 4) Restated: AM Sec.2-06.4.9.T: Revise the development package to provide refuse truck maneuverability onsite. Per TSM Sec.8-01.5.3.D metal container locations shall be placed so that the collection vehicle does not have to back into the public right-of-way or into moving traffic. As proposed the refuse truck will back out into Herbert Ave (a named street) and could pose an unsafe point for the pedestrians and bike riders who use this public right-of-way for access. This type of collection requires prior approval from Environmental Services (ES) in writing and any deviation from the standard will require a Technical Standard Modification Request (TSMR). 5) Restated: AM Sec.2-06.4.9.T: Revise the development package to provide a General Note on the Development Package (DP14-0241) referencing the TSMR Case #, date of approval and any conditions (if applicable). GENERAL COMMENTS: Please provide a revised Development Package that addresses the comment provided above. For expedite purposes the development package can be reviewed over the counter (PDSD Engineering Division comment only) for stamp approval once all items have been addressed. Please call to schedule an appointment when ready. For any questions or to schedule meetings call me at 837-4929. Jason Green, CFM Senior Engineer Associate Engineering Division Planning & Development Services Department |
| 07/02/2015 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 07/02/2015 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 07/06/2015 | ANDREW CONNOR | LANDSCAPE | REVIEW | Approved | |
| 07/16/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 07/16/2015 | PATRICIA GEHLEN | ZONING-DECISION LETTER | WRITE DECISION LETTER | Reqs Change | This review has been completed and resubmittal is required. Please resubmit the following items: 1) Two rolled sets of the plans 2) All items required by review staff 3) All items needed to approve this plan |
| 07/16/2015 | DAVID RIVERA | H/C SITE | REVIEW | Approved |