Permit Review Detail
Review Status: Completed
Review Details: RESUB - SITE and/or GRADING
Permit Number - DP14-0223
Review Name: RESUB - SITE and/or GRADING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/01/2015 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 04/09/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 04/15/2015 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 04/16/2015 | JOE LINVILLE | LANDSCAPE | REVIEW | Passed | |
| 04/20/2015 | RONALD BROWN | HC SITE | REVIEW | Reqs Change | For both ramps at the accessible route to Sport Road: a. The reference to detail 4B/C3 is not acceptable. This is a COT DOT 207 detail that is for right of way accessible code compliance only. It is not to be used on private projects. The governing accessible code for this project is as stated on sheet T1, "the 2012 IBC, Chapter 11 and the 2009 ICC A117.1. b. For the most easterly ramp provide flared sides as per the 2009 ICC A117.1, Section 406 with flared side at a maximum sope of 1:10. c. For the most Westerly ramp either provide flared sides at a 1:10 slope mximum or delete the flared side and provide a return curb on both sides. END OF REVIEW |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/22/2015 | KROBLES1 | OUT TO CUSTOMER | Completed |