Permit Number: DP14-0185
Parcel: 13216600A

Address:
4004 S PARK AV

Review Status: Completed

Review Details: SITE and/or GRADING

Permit Number - DP14-0185
Review Name: SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/10/2014 MICHAEL ST. PAUL ZONING REVIEW Reqs Change This is not ready for submittal. Dimensins are required for tje PAAL and the parking spaces.
10/10/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
10/10/2014 LOREN MAKUS ENGINEERING REVIEW Approved
10/14/2014 ANDREW CONNOR NPPO REVIEW Approved
10/14/2014 MARTIN BROWN FIRE REVIEW Approved
10/14/2014 RONALD BROWN H/C SITE REVIEW Passed
10/14/2014 ANDREW CONNOR LANDSCAPE REVIEW Approv-Cond ENSURE THAT ALL ZONING COMMENTS ARE ADDRESSED PRIOR TO LANDSCAPE APPROVAL SIGNATURE.
10/14/2014 RBROWN1 ADA REVIEW Reqs Change 1. The north curb ramp referes to detail 3/A1.2 Threre is no detail 3/A1.2.
2. Provide detail 3/A1.2 as per the requirements of the 2010 ADASAD section 406 and refer the eastern curb ramp. Show all accessible requirements such as dimensioning, slopes, flared sides slope and landing clearances.
3. Provide an accessible emergeny egress from the enclosed parking area to the public right of way.
4. At the north accessible parking group, provide a minimum of 2% grade slope in all directions. Do not leave this up to the GC to confirm.
a. Same requirements for the 2 accessible parking spaces shown in the middle parking aisles.
5. The generic accessible parking plan is not the same as what is designed and shown on the parking lot plans. Generic plans are not acceptable. Provide large scale plans of both accessible layouts showing all accessible requirements.
6. The accessible parking aisle is not dimensioned properly at the middle accessible parking group.
END OF REVIEW

Final Status

Task End Date Reviewer's Name Type of Review Description
10/15/2014 FERNE RODRIGUEZ OUT TO CUSTOMER Completed