Permit Number: DP14-0171
Parcel: 110161150

Address:
6019 E GRANT RD

Review Status: Completed

Review Details: SITE and/or GRADING

Permit Number - DP14-0171
Review Name: SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/05/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide the size of the private sewer pipe to which the office will be connected and the elevation of the upstream and downstream cleanouts. Show the first floor elevation for the new building on the site plan. [Initial comment: Provide the size of the private sewer pipe to which the office will be connected and the elevation of the upstream and downstream cleanouts. Show the elevation of the finished floor. If the finished floor elevation of the building is less than 12 inches above the elevation of the next upstream cleanout in the private sewer collection system, a backwater valve shall be installed in the building sewer.]
11/10/2014 KEN BROUILLETTE FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/10/2014 SHANAE POWELL OUT TO CUSTOMER Completed