Permit Number: DP14-0171
Parcel: 110161150

Address:
6019 E GRANT RD

Review Status: Completed

Review Details: SITE and/or GRADING

Permit Number - DP14-0171
Review Name: SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/25/2014 MARTIN BROWN FIRE REVIEW Denied Please indicate location of existing and/or proposed fire hydrants, with dimensions to property lines. Chapter 5 of the 2012 International Fire Code gives guidance as far as spacing requirements.
Please indicate approximate location of underground fire sprinkler supply line and Fire Department Connection.
Please indicate on plans that fire sprinkler installation AND fire underground suppl;y line installation are deferred submittals requiring separate permits.
09/25/2014 RBROWN1 ADA REVIEW Passed
10/01/2014 RONALD BROWN H/C SITE REVIEW Approved
10/02/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. An approved development plan is not to be used for construction of on-site utilities (e.g. water service to the building, building sewer, site lighting, or electrical service to the building). The construction of the on-site utilities may be included with the permit for constructing the building or as a separate permit.
2. Provide the size of the private sewer pipe to which the office will be connected and the elevation of the upstream and downstream cleanouts. Show the elevation of the finished floor. If the finished floor elevation of the building is less than 12 inches above the elevation of the next upstream cleanout in the private sewer collection system, a backwater valve shall be installed in the building sewer.
10/07/2014 DAVID RIVERA ZONING REVIEW Approved
10/22/2014 ANDREW CONNOR LANDSCAPE REVIEW Approved
10/22/2014 ANDREW CONNOR NPPO REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/29/2014 CPIERCE1 REJECT SHELF Completed