Permit Review Detail
Review Status: Completed
Review Details: SITE and/or GRADING
Permit Number - DP14-0171
Review Name: SITE and/or GRADING
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/25/2014 | MARTIN BROWN | FIRE | REVIEW | Denied | Please indicate location of existing and/or proposed fire hydrants, with dimensions to property lines. Chapter 5 of the 2012 International Fire Code gives guidance as far as spacing requirements. Please indicate approximate location of underground fire sprinkler supply line and Fire Department Connection. Please indicate on plans that fire sprinkler installation AND fire underground suppl;y line installation are deferred submittals requiring separate permits. |
09/25/2014 | RBROWN1 | ADA | REVIEW | Passed | |
10/01/2014 | RONALD BROWN | H/C SITE | REVIEW | Approved | |
10/02/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. An approved development plan is not to be used for construction of on-site utilities (e.g. water service to the building, building sewer, site lighting, or electrical service to the building). The construction of the on-site utilities may be included with the permit for constructing the building or as a separate permit. 2. Provide the size of the private sewer pipe to which the office will be connected and the elevation of the upstream and downstream cleanouts. Show the elevation of the finished floor. If the finished floor elevation of the building is less than 12 inches above the elevation of the next upstream cleanout in the private sewer collection system, a backwater valve shall be installed in the building sewer. |
10/07/2014 | DAVID RIVERA | ZONING | REVIEW | Approved | |
10/22/2014 | ANDREW CONNOR | LANDSCAPE | REVIEW | Approved | |
10/22/2014 | ANDREW CONNOR | NPPO | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/29/2014 | CPIERCE1 | REJECT SHELF | Completed |