Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: DP14-0170
Parcel: 12701005D

Review Status: Completed

Review Details: RESUB - SITE and/or GRADING

Permit Number - DP14-0170
Review Name: RESUB - SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/16/2015 KEN BROUILLETTE FIRE REVIEW Approved
03/23/2015 LOREN MAKUS ENGINEERING REVIEW Approved
03/31/2015 RONALD BROWN HC SITE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/16/2015 KROBLES1 OUT TO CUSTOMER Completed