Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: DP14-0170
Parcel: 12701005D

Review Status: Completed

Review Details: RESUB - SITE and/or GRADING

Permit Number - DP14-0170
Review Name: RESUB - SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/04/2014 MICHAEL ST. PAUL ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Michael St Paul
Planning Technician

PROJECT: DP14-0170
5151 East Broadway Boulevard
Landscaping and Parking and Loading (OCR-2)

TRANSMITTAL DATE: December 4, 2014


COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Unified Development Code, The Administrative and Technical Manuals were addressed.

This plan has been reviewed for compliance with the Development Package Standards listed in section 2-06 of the City of Tucson Administrative Manual. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC).

The review comments include the actual standard first with the applicable Administrative Manual section number and the following paragraph is the actual comment related to the specific item that must be addressed. If you need to review the sections listed below click on the link or copy it in the address bar of your internet program. http://www.amlegal.com/nxt/gateway.dll/Arizona/tucson_az_udc/administrativemanual?f=templates$fn=default.htm$3.0$vid=amlegal:tucson_udc_az

This link will take you directly to the section used for the standards review. The UDC requirements are in the Unified Development Code and can be viewed at the same web link as above

1. Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is .

2. SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS)
Section

2-06.1.0 GENERAL

2-06.2.0 APPLICATION SUBMITTAL REQUIREMENTS

2-06.3.0 FORMAT REQUIREMENTS

2-06.4.0 CONTENT REQUIREMENTS

2-06.1.0 GENERAL

2-06.1.1 PURPOSE
This standard has been prepared for the purpose of informing applicants of the submittal and review requirements for development package documents to assure proper and adequate information is presented in a consistent manner, thereby providing the basis for an efficient and timely review. The development package documents are prepared in support of applications for building permits and related reviews.

The information that is requested establishes the basis upon which the project will be approved and could affect what is required of the property in the future, should there be a proposal for expansion or for a different use of the property.

This standard does not waive any applicable city regulations or codes.

2-06.1.2 APPICABILITY
This standard shall be used for all site plans and tentative plats submitted to PDSD for review.

2-06.2.1 APPLICATION SUBMITTAL REQUIREMENTS
Development Package applications are available from PDSD. Completed applications and accompanying materials shall be submitted to PDSD. Incomplete or inaccurate applications will not be accepted, nor will any application in which the pre-application conference or neighborhood meeting requirements have not been met. The types of documents and the specific number of copies required of each of the documents are on the PDSD website or may be obtained from PDSD. Resubmittals of development packages require a comment response letter that details how all previous comments have been addressed. Provide the same number of copies of the comment response letter as plans provided.
The following documents and information shall be submitted upon application:

2-06.2.1 Application Form
A completed application signed by the property owner or authorized designee;

2-06.2.2 Development Package
A development package must be prepared to the format and content requirements described herein;

2-06.2.3 Related Reviews
In addition to the plan process, a project may require review for other types of plans and documents. The applications for those processes are submitted to the appropriate department for review and approval. These related reviews can be applied for so that review can occur concurrently with the development package application. However, it must be understood that, should the related application be approved subject to conditions or denied, this may affect the;

2-06.2.4 Concurrent Reviews
The development package is designed to allow for concurrent review of any site related reviews. Concurrent review means that all plans and documents needed for the review are submitted as one package. Examples of site related reviews include but are not limited to: site plans, landscape plans, NPPO plans, water harvesting plans, grading plans, SWPPP plans, floodplain use permits, and overlay reviews. Separate applications are often required for the different site related reviews even if the plans are submitted concurrently; and,

2-06.2.5 Fees
Fees in accordance with Section 4-01.0.0, Development Review Fee Schedule.

2-06.3.0 FORMAT REQUIREMENTS

2-06.3.1 - Each sheet shall measure 24 inches by 36 inches and include a minimum one inch margin on left side and one-half inch margin on all other sides to facilitate efficient record keeping. A larger sheet format may be used with the approval of the Planning and Development Services Department (PDSD).

2-06.3.2 - All mapped data shall be drawn at an engineering scale having no more than 50 feet to the inch. This scale is the minimum accepted to assure the plan will be legible during review and when digitized and/or reduced for record-keeping purposes. The same scale shall be used for all sheets within the set. Smaller scales (60:1 or greater) may be used for some or all of the sheets with the prior approval of PDSD when it is determined legibility and the ability to be digitized and/or reduced for archiving will not be affected.
2-06.3.3 - All lettering and text (upper or lower case), and numbering, shall be a minimum of three-thirty-seconds inches in height to assure the plan will be legible during review and when digitized and/or reduced for archiving.


2-06.3.11 - A key plan (if provided) shall be located on the first sheet.

1) COMMENT: Provide the key plan on the first sheet. PROVIDED

2-06.3.12 - An index of sheets in the development package shall be provided on the first sheet.

2) COMMENT: The sheet index should have the continuous number system. It is a good idea to provide both numbering systems as a cross reference to both the numbering systems on the sheets. PROVIDED

2-06.4.0 CONTENT REQUIREMENTS

2-06.4.1 - The name, mailing and email addresses, and phone number of the primary property owner of the site, the developer of the project, registrant(s), and other person(s), firm(s), or organization(s) that prepared the development package documents shall be provided on the right half of the cover sheet. The applicable registration or license number shall be provided if prepared by or with the assistance of a registered professional, such as a surveyor, architect, landscape architect, or engineer. All sealing shall be consistent with Arizona Board of Technical Registration guidelines.

3) COMMENT: Provide an email address for the owners. PROVIDED

2-06.4.2.D - The page number and the total number of pages in the package (i.e., sheet xx of xx).

4) COMMENT: See comment number two (#2). PROVIDED

2-06.4.3 - The administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet.

5) COMMENT: Provide the Development Package number (DP14-0170) in the lower-right corner of each sheet. PROVIDED

2-06.4.5 - When the development package documents consists of more than one sheet, a sheet index (a legible drawing of the site showing the area represented on each sheet) is to be placed on the cover sheet or the second sheet.

6) COMMENT: Depict and identify the individual sheets of the site plan on the cover drawing. PROVIDED

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes

2-06.4.7.A.8.a - Floor area for each building;

7) COMMENT: The approximate floor areas of each building do not match the last approved development plans (D11-0022 and D06-0050). Revise the plans to match the last approved plans. ADDRESSED; except the storage building.

2-06.4.7.A.8.d - When the proposed site is part of a larger site, the calculations encompass the entire site, whether existing or proposed. If the project is being phased, calculations must show that, at each phase, requirements are being met.

8) COMMENT: Revise the calculations for vehicle parking, bicycle parking and loading spaces to reflect the correct square footage of the buildings and current code. There is also an additional building in the northeast corner of the site. ADDITION TO COMMENT: The storage building (container) requires a permit for its location and if it exceeds two hundred (200) square feet it also requires a building permit. This building must be included in the parking calculation and also takes out parking spaces.

2-06.4.8 - Existing Site Conditions
The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided.

9) COMMENT: Provide all of the above information on the site plan. PROVIDED

2-06.4.8.A - Provide site boundary/subdivision perimeter information, including bearing in degrees, minutes, and seconds, with basis for bearing noted, together with distances in feet, to hundredths of a foot, or other functional reference system.

10) COMMENT: Provide the bearing and lot dimensions on the site plan. PROVIDED

2-06.4.8.B - All easements shall be drawn on the plan. The recordation information, location, width, and purpose of all easements on site will be stated. Blanket easements should be listed in the notes, together with recordation data and their proposed status. Should an easement not be in use and be proposed for vacation or have been abandoned, so indicate. However, should the easement be in conflict with any proposed building location, vacation of the easement shall occur prior to approval of plan unless written permission from easement holder(s) is/are provided.

11) COMMENT: Provide all the above information for existing easements on the site plan. PROVIDED

2-06.4.8.C - The following information regarding existing private or public right-of-way adjacent to or within the site shall be provided: the name, right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts, and sidewalks.

12) COMMENT: Provide all of the above information regarding the existing right-of-way on the site plan. PROVIDED

2-06.4.8.D - The following information regarding existing utilities shall be provided: the location and size of water wells, water pumping plants, water reservoirs, water lines, fire hydrants, sanitary and storm sewers, including the pipe diameter and the invert and rim elevations of all manholes and cleanouts; the Pima County Wastewater Management Department (PCWMD) reference number; locations of gas lines, electric and telephone lines, poles, and communications cables, on-ground junction boxes, and street lights. If water mains and sewers are not located on or adjacent to the tract, indicate the direction, distance to, and sizes of those nearest the property.
Identifying the locations of all utilities and service equipment immediately adjacent to the project is especially important in situations where pedestrian and vehicular access and circulation or landscaping can be in conflict. By knowing the location of the existing utilities, design of the project can take those elements into consideration and can help avoid expensive and time-consuming relocation of utilities, major redesign, or requests to vary regulations after commencement of construction.

13) COMMENT: Identify and depict all existing utilities, as described above, on the site plan. PROVIDED

2-06.4.8.G - Other significant conditions on the site, such as major rock outcrops, structures, fences, walls, etc., shall be shown. These elements should be indicated in a different line weight than the proposed improvements and labeled "to be removed" or "to be retained."

14) COMMENT: There is a building in the northeast parking area that is not depicted on the plan. Place that building on the plan and include it in the project calculations. The building may need a building permit. ADDITION TO COMMENT: The storage building must be included in the calculations: See comment 8.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

2-06.4.9.F - All existing zoning classifications on and adjacent to the project (including across any adjacent right-of-way) shall be indicated on the drawing with zoning boundaries clearly defined. If the property is being rezoned, use those boundaries and classifications. The basis for this requirement is that some zoning requirements on a project are based on the zoning classification of adjacent property. Also, in some instances, each zone has to be taken into consideration on property that is split by two or more zoning classifications, as each may have different requirements.

15) COMMENT: Provide the zoning classifications for the adjacent properties on the site plan. PROVIDED

2-06.4.9.H - Proposed Traffic Circulation

2-06.4.9.H.2 - Show future and existing sight visibility triangles. On a designated MS&R street, the sight visibility triangles are based on the MS&R cross-section.

16) COMMENT: Delineate, with dimensions, the existing and future sight-visibility triangles (SVTs) on the site plan. PROVIDED

2-06.4.9.H.4 - Indicate if existing streets are public or private; provide street names, widths, curbs, sidewalks, and utility locations, all fully dimensioned.

17) COMMENT: Provide all of the above information for the existing streets on the site plan. PROVIDED

2-06.4.9.H.5 - If utilizing parking area access lanes (PAALs), they shall be designed in accordance with Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC.

18) COMMENT: Dimension all of the PAALs on the site plan. DID NOT PROVIDE.

2-06.4.9.H.5.a - Show all motor vehicle off-street parking spaces provided, fully dimensioned. As a note, provide calculations on the number of spaces required (include the ratio used) and the number provided, including the number of spaces required and provided for the physically disabled. The drawing should indicate parking space locations for the physically disabled. A typical parking space detail shall be provided for both standard parking spaces and those for the physically disabled. For information on parking requirements for the physically disabled, refer to adopted building and accessibility codes of the City of Tucson. Design criteria for parking spaces and access are located in Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC.

19) COMMENT: Provide all the above information for the parking. Include dimensioned details. Revise the parking calculations to reflect the approved square footage of the buildings on the approved plans. Also include the building, in the parking area, on the northeast corner of the property. PROVIDED

2-06.4.9.H.5.c - Show all loading zones, vehicle maneuverability fully dimensioned, and access route. Provide as a note the number of loading spaces required, the number provided, whether the loading space is a Type A or B as provided in UDC Section 7.5.4.

20) COMMENT: Two (2) Type A loading spaces are required. Two loading spaces are depicted on the previously approved plans. Provide the required loading spaces and provide the calculations for the loading spaces. PROVIDED

2-06.4.9.H.5.d - Show bicycle parking facilities fully dimensioned. For specifics, refer to Section 7.4.9, Bicycle Parking Design Criteria, of the UDC. Provide, as a note, calculations for short and long term bicycle spaces required and provided.

21) COMMENT: Short-term bicycle parking must be provided within fifty (50) feet of each public entrance to a building as measured along the most direct pedestrian access route (UDC Section 7.4.9.C.2.a and Figure 7.4.9-A). SEE ADDITION TO COMMNET BELOW.
Short-term bicycle parking: "An access aisle at least five feet wide must be provided between two rows of bicycle parking. The aisle width is measured between the lengthwise dimensions (i.e., six feet) of the bicycle parking spaces between the two rows ((UDC Section 4-7.4.9.B.2.h). Provide fully dimensioned plan views of the bicycle parking. See the "General Criteria" for "Parking and Maneuvering" (UDC Section 7.4.9.B). Provide lighting (UDC Section 7.4.9.B.1.e).
Long-term bicycle parking: Provide all the required information for long-term bicycle parking (UDC Section 7.4.9.D). Provide dimension plans and details.
ADDITION TO BICYCLE PARKING COMMENT: Provide short-term bicycle parking with fifty (50) feet of each public entrance (as stated above). Demonstrate with dimensions on the site plan (UDC Section 7.4.9.C.2.a). "Where buildings have more than one public entrance or a site has more than one building, short-term bicycle parking must be distributed so that at least one short-term parking space is within 50 feet of each public entrance" (UDC Section 7.4.9.C.2.d). The short-term bicycle parking must also be "Clearly visible from the adjacent sidewalks, drives, and/or public entrances(s)" (UDC Section 7.4.9.C.2.c), and "outside the building(s)" (UDC Section 7.4.9.C.2.b). Provide the short-term bicycle parking as required near all the public entrances.

2-06.4.9.J - If street dedication is not required or proposed and the project site is adjacent to a Major Street or Route, draw the Major Street right-of-way lines for those streets. (Add the MS&R future sidewalk, right-of-way lines, sight visibility triangles, etc.)

22) COMMENT: Delineate and dimension all of the future right-of-way (F/ROW) information for Broadway and Rosemont on all of the plans. PROVIDED

2-06.4.9.L - All proposed easements (utility, sewer, drainage, access, etc.) are to be dimensioned and labeled as to their purposes and whether they will be public or private. The easements may have to be recorded and the recordation information added to the development package prior to approval.

23) COMMENT: Provide any proposed easement information, as described above, on the site plans. PROVIDED

2-06.4.9.Q - Provide the square footage and the height of each commercial, industrial, or business structure and the specific use proposed within the footprint of the building(s).

24) COMMENT: Revise the square footage of the building to match the approved. ADDITION TO COMMENT: The square footage has been properly addressed for the two main building. The square footage for the storage building must be provided.

2-06.4.9.R - Show on-site pedestrian circulation and refuge utilizing location and the design criteria in Section 7-01.0.0, Pedestrian Access, of the Technical Standards Manual.

25) COMMENT: Show the pedestrian circulation as described above. PROVIDED

2-06.4.9.W - Indicate the locations and types of proposed signs (wall, free-standing, pedestal) to assure there are no conflicts with other requirements and that minimal locational requirements can be met. Indicate if there are any existing billboards on site. Compliance to the Sign Code, Chapter 3 of the Tucson Code, is required.

26) COMMENT: Any new signs shall require a separate permit process. ADDRESSED

2-06.4.9.X - Show compliance with landscaping and screening requirements by locations, material descriptions, and dimensions. Specific plant or hardscape material shall be detailed on a landscape plan. A detailed landscape plan is required in accordance with Section 2-11.0.0, Landscape Plan Requirements.

27) COMMENT: See Landscaping review comments. ADDRESSED

If you have any questions about this transmittal, please call Michael St. Paul, (520) 837-4959 or send an email to Michael.StPaul@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package site plan and any requested documents.
12/12/2014 ANDREW CONNOR LANDSCAPE REVIEW Approv-Cond Ensure that all Zoning comments and concerns are addressed prior to Landscape/ NPPO approval signature.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/30/2014 KROBLES1 APPROVAL SHELF Completed
12/30/2014 KROBLES1 OUT TO CUSTOMER Completed
12/30/2014 CPIERCE1 REJECT SHELF Completed