Permit Review Detail
Review Status: Completed
Review Details: DEV PKG - RESUBMITTAL
Permit Number - DP14-0146
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/07/2014 | AROMERO4 | START | PLANS SUBMITTED | Completed | |
| 11/14/2014 | MARTIN BROWN | COT NON-DSD | FIRE | Approved | |
| 12/02/2014 | RONALD BROWN | ZONING HC | REVIEW | Reqs Change | SHEET C1.3 1. At note 18 delete all references to ADAAG. a. The governing accessibility code is the 2012 IBC, Chapter 11 and the 2009 ICC A117.1. b. All ramps are to be as per the 2009 ICC A117.1, Sections 405 and/or 406 as applicable. c. Detectable warnings strips (truncated domes) are required at transportation platforms only. 2. Add another note 23: "All accessible route slopes are to comply with the 2009 ICC A117.1, Section 403.3; 5% maximum running slope and 2% maximum cross slopes." SHEET C3.1 3. The "F" note reference at the accessible parking ramps should reference to the accessible parking blow up datail on sheet 7.2. SHEET C7.1 4. At the accessible ramp in sidewalk detail: a. Reference comment 1c above. They may be installed at the owner's option and if so must follow the requirements of the 2009 ICC A117.1, Sections 406.12, 13, 14 and 705 as applicable. END OF REVIEW |
| 12/02/2014 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 12/05/2014 | ANDREW CONNOR | LANDSCAPE | REVIEW | Reqs Change | Identification and Descriptive Data All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan. LANDSCAPING AND SCREENING Minimum Width The street landscape border is a minimum of ten feet wide. Dimension street landscape orders on Oracle & Wetmore Rd's Street landscape borders must be located entirely on site, except that, if approved by the City Engineer or designee, up to five feet of the required ten foot width may be placed within the adjacent right-of-way area or within the Major Streets and Routes (MS&R) right-of-way area on MS&R streets. Use of ROW on Oracle Rd will require ADOT approval. Inorganic Ground Cover Except as otherwise provided by this section, the area between the right-of-way line and sidewalk and the area between the sidewalk and the curb, if not covered with vegetation, must be covered with an appropriate inorganic ground cover, such as decomposed granite. Continuous screens along street frontages for vehicle use area must be as determined by Table 7.6.4-I. Provide appropriate screening. Identify screening elements. Vegetative Screens Vegetation used to meet the screening standards is not included in the ground cover calculation as provided in Section 5-01.5.3, Calculation of Plant Growth Coverage. Hedges and other vegetative screens may not extend more than three feet into the street landscape border Ensure that all Zoning and Engineering comments and concerns are addressed. Additional comments may apply |
| 12/05/2014 | TOM MARTINEZ | OTHER AGENCIES | AZ DEPT TRANSPORTATION | Approved | The Arizona Department of Transportation (ADOT) reviewed the response to our review comments below, and we have no further comments regarding the Development Plans for the proposed Longhorn Steakhouse to be located on the west side of SR 77 (Oracle Road) north of the Oracle Road/Wetmore Road intersection. Thank you for the opportunity to comment on the Development Plans. We are looking forward to working with the City of Tucson towards the satisfactory completion of the development. Maria Deal Transportation Engineering Specialist 1221 S. 2nd Ave. Tucson, AZ 85713 520.388.4235 mdeal@azdot.gov |
| 12/08/2014 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 12/09/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 12/10/2014 | PATRICIA GEHLEN | ZONING-DECISION LETTER | REVIEW | Reqs Change | This review has been completed and resubmittal is required. Please resubmit the following items: 1) Two rolled copies of the plans 2) All items requested by reveiw staff 3) All items needed to approve this plan |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/23/2014 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |