Permit Number - DP14-0112
Review Name: SITE and/or GRADING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/26/2014 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 06/26/2014 | RBROWN1 | ADA | REVIEW | Passed | |
| 06/26/2014 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 06/26/2014 | RONALD BROWN | H/C SITE | REVIEW | Reqs Change | SHEET A00.05 1. At details 4 and 6, change the height of the signs to 7'-0" a.f.g. 2. At detail 2: Relocate the accessible signs to a position just inside the curb line. 3. Reference ramp to detail 7/A00.05 4. Delete all references to ADA. Accessible regulations are as the 2012 IBC, Chapter 11 and 2009 ICC A117.1. SHEET C2 5. At the Access Ramp w/Wings, call out a maximum slope of 1:12 at the ramp and a 1:10 maximum slope at the flared sides. 6. The City of Tucson letterning height standard is 3/32" minimum, actual height for both upper and lowe case. Revise all non-compliant drawings and resubmit. END OF REVIEW |
| 06/27/2014 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 06/27/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 07/07/2014 | SPOWELL1 | LANDSCAPE | REVIEW | Needs Review | |
| 07/07/2014 | SPOWELL1 | NPPO | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/07/2014 | SHANAE POWELL | OUT TO CUSTOMER | Completed |