Permit Number: DP14-0065
Parcel: 12112401A

Address:
5326 E PIMA ST

Review Status: Completed

Review Details: SITE and/or GRADING

Permit Number - DP14-0065
Review Name: SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/28/2014 RBROWN1 ADA REVIEW Passed
04/29/2014 STEVE SHIELDS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: 5326 E. Pima Street
Development Package (1st Review)
DP14-0065

TRANSMITTAL DATE: April 29, 2014

DUE DATE: May 23, 2014

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

The review comments include the actual standard first with the applicable Administrative Manual section number and the following paragraph is the actual comment related to the specific item that must be addressed. If you need to review the sections listed below click on the link or copy it in the address bar of your internet program. http://www.amlegal.com/nxt/gateway.dll/Arizona/tucson_az_udc/administrativemanual?f=templates$fn=default.htm$3.0$vid=amlegal:tucson_udc_az

This link will take you directly to the section used for the standards review. The UDC & TSM requirements are in the Unified Development Code and can be viewed at the same web link as above

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is April 24, 2015.

SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS)

2-06.1.0 GENERAL

2-06.1.1 PURPOSE
This standard has been prepared for the purpose of informing applicants of the submittal and review requirements for development package documents to assure proper and adequate information is presented in a consistent manner, thereby providing the basis for an efficient and timely review. The development package documents are prepared in support of applications for building permits and related reviews.

The information that is requested establishes the basis upon which the project will be approved and could affect what is required of the property in the future, should there be a proposal for expansion or for a different use of the property.

This standard does not waive any applicable city regulations or codes.

2-06.1.2 APPICABILITY
This standard shall be used for all site plans and tentative plats submitted to PDSD for review.

2-06.2.2 Development Package
A development package must be prepared to the format and content requirements described herein;

2-06.3.0 FORMAT REQUIREMENTS

2-06.3.12 - An index of sheets in the development package shall be provided on the first sheet.

1. COMMENT: The drawing index does not include sheets 5 &6.

CONTENT REQUIREMENTS

2-06.4.3 - The administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet.

2. COMMENT: Provide the development case number, DP14-0065, on all sheets adjacent to the title block.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes

2-06.4.7.A.4 - Identify the existing and proposed use of the property as classified per the UDC. List all UDC sections applicable to the proposed uses.

3. COMMENT: General note 4 lists the proposed use as "CIVIC USE". "CIVIC" is a use group not a use, provide the proposed use in the general note. Per phone conversation, 4/29/14, this plan has been reviewed as a Religious Use.

2-06.4.7.A.6 - If a plan or plat is prepared in conjunction with other applications or overlays or the parcel being developed is subject to conditions of an application processed previously, additional information must be added to the plan. Such applications and overlays include, but are not limited to: annexations; rezonings; special exceptions; Board of Adjustment variances; Design Development Options; Technical Standard Modification Request; overlays (Airport Environs Zone, Environmental Resource Zone, Gateway Corridor Zone, Hillside Development Zone, Historic Preservation Zone, Major Streets and Routes, Rio Nuevo District, Scenic Corridor Zone, WASH); Modification of Development Regulations through the Downtown Area Infill Incentive District or Rio Nuevo District; Downtown Heritage Incentive Zone; or, Design Review Board. Provide the following information on the plan.

4. COMMENT: Provide a general note on the cover sheet stating "THIS PROJECT IS DESIGNED TO MEET THE OVERLAY ZONE(S) CRITERIA, UDC ARTICLE 5.4 MAJOR STREETS AND ROUTES SETBACK ZONE (MS&R)."

2-06.4.8 - Existing Site Conditions
The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided.

2-06.4.8.C - The following information regarding existing private or public right-of-way adjacent to or within the site shall be provided: the name, right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts, and sidewalks.

5. COMMENT: Provide dimensions for the location of the existing curb and sidewalk width on the plan.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

2-06.4.9.F - All existing zoning classifications on and adjacent to the project (including across any adjacent right-of-way) shall be indicated on the drawing with zoning boundaries clearly defined. If the property is being rezoned, use those boundaries and classifications. The basis for this requirement is that some zoning requirements on a project are based on the zoning classification of adjacent property. Also, in some instances, each zone has to be taken into consideration on property that is split by two or more zoning classifications, as each may have different requirements.

6. COMMENT: Provide the zoning for the parcels located north of Pima Street.

2-06.4.9.H.2 - Show future and existing sight visibility triangles. On a designated MS&R street, the sight visibility triangles are based on the MS&R cross-section.

7. COMMENT: Provide the required SVT's on the plan including the future SVT's if applicable.

2-06.4.9.H.5 - If utilizing parking area access lanes (PAALs), they shall be designed in accordance with Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC.

8. COMMENT: Per UDC Article 7.4.6.H.1 Barriers, such as post barricades or wheel stop curbing, are required in a vehicular use area to prevent vehicles from extending beyond the property lines, to prevent cars from damaging adjacent landscaping, walls, or buildings, overhanging adjacent sidewalk areas, and/or driving onto unimproved portions of the site. That said some type of barrier is required along the southeast end of the vehicle parking area and around the three (3) landscape islands shown on the plan.

2-06.4.9.H.5.a - Show all motor vehicle off-street parking spaces provided, fully dimensioned. As a note, provide calculations on the number of spaces required (include the ratio used) and the number provided, including the number of spaces required and provided for the physically disabled. The drawing should indicate parking space locations for the physically disabled. A typical parking space detail shall be provided for both standard parking spaces and those for the physically disabled. For information on parking requirements for the physically disabled, refer to adopted building and accessibility codes of the City of Tucson. Design criteria for parking spaces and access are located in Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC.

9. COMMENT: Provide an accessible vehicle parking space detail.

2-06.4.9.H.5.d - Show bicycle parking facilities fully dimensioned. For specifics, refer to Section 7.4.9, Bicycle Parking Design Criteria, of the UDC. Provide, as a note, calculations for short and long term bicycle spaces required and provided.

10. COMMENT: Based on the "BIKE REACK SPACING" detail sheet 4 there are four (4) short term bicycle parking spaces provided, not two (2) as listed in the short term bicycle parking space calculation on sheet 1. Clarify which number is correct.

11. COMMENT: Per UDC Article 7.4.9.B.2.f. A bicycle rack must be a minimum of two and one half feet from a wall or other obstruction. Clarify what the circle is that is shown on the "BIKE REACK SPACING" detail sheet 4 and if this is an obstruction show the required 2'-6" dimension on the detail.

12. COMMENT: Per UDC Article 7.4.9.B.2.f. A bicycle rack must be a minimum of two and one half feet from a wall or other obstruction. As a vehicle, obstruction, can park adjacent to the short term bicycle parking spaces show the required 2'-6" dimension on the detail.

13. COMMENT: Show the location of the required long term bicycle parking on the plan.

2-06.4.9.R - Show on-site pedestrian circulation and refuge utilizing location and the design criteria in Section 7-01.0.0, Pedestrian Access, of the Technical Standards Manual.

14. COMMENT: Demonstrate on the plan that the proposed accessible vehicle parking space signs will not reduce the sidewalk to less that 4'-0".

2-06.4.9.T - Show refuse collection areas, including locations of dumpsters, screening location and materials, and vehicle maneuverability, fully dimensioned, and access route. If dumpster service is not proposed, indicate type of service. For specific information on refuse collection, refer to Section 8-01.0.0, Solid Waste and Recycle Disposal, Collection, and Storage, of the Technical Standards Manual. Refuse collection on all projects shall be designed based on that section, even if collection is to be contracted to a private firm.

15. COMMENT: Show the refuse collection area on the plan.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
.
04/30/2014 MARTIN BROWN FIRE REVIEW Denied 1) Per section 503.2.5 of the 2012 International Fire Code, dead end fire apparatus access roads in excess of 150' in length shall be provided with an approved area for turning around fire apparatus.
2) Please provide location of any proposed and/or exiting fire hydrants, with dimensions to property lines.
05/01/2014 JASON GREEN ENGINEERING REVIEW Reqs Change DATE: May 5, 2014
SUBJECT: Kadampa Meditation Center Development Plan Package- Engineering Review
TO: Metro TED; Attn: Lisa Bowers
LOCATION: 5326 E Pima St; T14S R14E Sec02
REVIEWERS: Jason Green, CFM
ACTIVITY: DP14-0065


SUMMARY: Engineering Division of Planning & Development Services Department has received and reviewed the proposed Development Plan Package and Drainage Report (Cypress Civil Development, 07APR14) and Geotechnical Evaluation (Speedie and Associates, 18APR14). Engineering Division does not recommend approval of the Development Plan Package at this time. This review falls under the Unified Development Code (UDC), Administration Manual (AM) and Technical Standards Manual (TSM). Refer to the following link for further clarification:
http://www.amlegal.com/nxt/gateway.dll/Arizona/tucson_az_udc/administrativemanual?f=templates$fn=default.htm$3.0$vid=amlegal:tucson_udc_az

The following items need to be addressed:

SITE PLAN:

1) AM Sec.2-06.3.12: Revise the development plan package and Sheet Index on Sheet 1 to include Sheet 5 and 6.

2) AM Sec.2-06.4.3: The relevant Development Plan Package case number (DP14-0065) may be added to the lower right hand corner of the plan on all sheets.

3) AM Sec.2-06.4.7.A.6: Revise the development plan package to provide a General Note to read per the referenced section for the overlay(s) applicable to the site, specifically state that "the project is designed to meet the overlay zone criteria for Sec.5.4, Major Streets and Routes (MS&R) Setback Zone.

4) AM Sec.2-06.4.8.B: Provide written approval from all parties having a vested interest in the existing easements (15' Water Easement and 20' Flowage of Water and Debris Easement) along the south portion of the site. The plan proposes a CMU block wall within the easements and can not be approved and constructed until the written authorization is provided. Verify that the wall location does not damage the existing infrastructure within the easement.

5) AM Sec.2-06.4.8.C: Revise the development plan package to dimension the existing width of paving, curbs, curb cuts, and sidewalks within the public right-of-way.

6) AM Sec.2-06.4.9.H.1: Revise the development plan package to label the required minimum 25-foot radii at the new driveway entrance per TSM Sec.10-01.3.2.C and Figure 6.

7) AM Sec.2-06.4.9.H.1:Revise the development plan package to label and dimension the proposed driveway setbacks from adjacent driveways and/or street intersections along with any existing street lights, fire hydrants, electrical pole, etc per Chapter 25 of the Tucson Code Sec.25-38. It appears that there is an existing driveway located to the east of the property that may interfere with the required 25-foot curb returns and driveway location for this project.

8) AM Sec.2-06.4.9.H.1: Revise the development plan package to verify conformance with handicap accessibility for the existing sidewalk within the public right-of-way. Provide existing longitudinal and cross slopes to ensure maximum 2% or provide written approval from TDOT Permits and Codes that the existing sidewalk meets accessibility requirements.

9) AM Sec.2-06.4.9.H.1: Revise the development plan package to label the required handicap access ramps at the driveway location per 10-01.3.3.E. Label a Keynote in plan view to ensure that the ramps are constructed under this project and provide a description of the Keynote in the Keynote Legend to verify conformance with PC/COT Standard Detail #207. Once the curb returns are constructed the handicap access ramps must meet the minimum standards.

10) AM Sec.2-06.4.9.H.2: Revise the development plan package to label and dimension the existing and/or future SVTs for the driveway entrance, refer to TSM Sec.10-01.5.3 for line of sight matrix. On a designated MS&R street, the SVTs are based on the MS&R cross-section.

11) AM Sec.2-06.4.9.H.5.a: Revise the development plan package to clearly label the required separation of the proposed vehicular use area and the unused portions of the site not for vehicular use. Refer to UDC Sec.7.4.6.H.1; A barrier, such as post barricades or wheel stop curbing, are required in a vehicular use area to prevent vehicles from extending beyond project area, damaging adjacent landscaping, fencing, or unpaved areas, and/or driving onto unimproved portions of the site. Provide a barrier around the south side of the back up spur and adjacent to the water harvesting area and around all proposed interior landscape islands located within the parking lot in order to meet this requirement.

12) AM Sec.2-06.4.9.J: Revise the development plan package to label the dimensioned right-of-way for Pima Street as "Future/Existing."

13) AM Sec.2-06.4.9.J: Revise the development plan package to verify the future sidewalk area. Label and dimension the MS&R future sidewalk area and the future sight visibility triangles if the current location does not meet the MS&R future dimensions.

14) AM Sec.2-06.4.9.M: Revise the development plan package and Paving and Grading Note #13 to remove the reference to the SWPPP Inspection. The site does not require a SWPPP therefore only the grading preconstruction meeting is required.

15) AM Sec.2-06.4.9.M: Revise the development plan package to provide a General Note to state; "Approval from TDOT Permits and Codes for all improvements within the public right-of-way will be required. A right-of-way use permit application will be required prior to construction."

16) AM Sec.2-06.4.9.M: Revise the development plan package to provide a General Note that includes the reference to the Geotechnical Report and any addendums prepared for this project. Provide the date, job number, engineer who prepared the report, etc.

17) AM Sec.2-06.4.9.M: Revise the development plan package to provide a General Note to state; "All proposed fencing and walls will require a separate permit for review and approval by all necessary Planning Development Services Departments."

18) AM Sec.2-06.4.9.M: Revise the development plan package to provide cross-sections at the property lines at the location of the proposed CMU wall to verify that the wall is designed to be fully constructed onsite. The wall and footer along with all disturbances to construct the wall must be located on the subject parcel. If the construction of the wall requires disturbance on adjacent properties then a written notarized agreement will be required along with a temporary construction easement.

19) AM Sec.2-06.4.9.N.3: Revise the development plan package to clearly label all existing drainage infrastructure with Improvement Plan #, slopes, inlet elevation (upstream and downstream), etc. that is in the existing right-of-way.

20) AM Sec.2-06.4.9.N.3: Revise the development plan package and Keynote #8 to correctly label the existing sidewalk scupper located within the right-of-way. The Keynote calls it out as a culvert. If a culvert is existing provide the invert elevations for the inlet and outlet and the culvert slope.

21) AM Sec.2-06.4.9.R: Refer to comments from Ron Brown, RA Structural Plans Examiner for all handicap accessibility comments that may be associated with this project. Specifically the onsite handicap access ramps must meet ANSI requirements and can not be built to the PC/COT Standard Detail #207, this detail is for ramps in the right-of-way only.

22) AM Sec.2-06.4.9.R: Revise the development plan package to label the required landing and or clear 4-foot sidewalk adjacent to both proposed onsite handicap access ramp locations. Verify that the ramps meet the minimum ANSI requirements.

23) AM Sec.2-06.4.9.T: Revise the development plan package to provide for centralized onsite solid waste and recycle collection service pick up per TSM Sec.8-01.5.1.A. Provide specific details on the development plan document for construction purposes. The details must match TSM Sec.8-01, Figure 2 and Figure 3a for the required double enclosure walls with gates, concrete thickness and compressive strength, concrete approach apron dimensions, space from wall to bollards, anchoring bolts, 14'x40' clear approach for each container, etc. Or provide approval from ES if refuse service is proposed using APC. The development plan package has conflicting information throughout on how the refuse service is to be handled. Calculations on Sheet 1, versus to the 2 Keynotes (#19 and 26) on Sheet 2 and the enclosure detail on Sheet 4. Also the post developed watershed map in the drainage report shows excess impervious cover due to more vehicular use area and a refuse enclosure.

DRAINAGE REPORT:

24) Revise the Drainage Report to provide a discussion on the existing 20' flowage of water and debris easement located along the south portion of the site. Along with the discussion and written approval from all parties who have a vested interest in the easement provide calculations for the proposed wall openings to verify that the wall does not encroach or adversely effect surrounding properties.

25) Revise the Drainage Report and proposed watershed map to match the proposed development plan package. The watershed map shows excess impervious area and a refuse enclosure that is not shown on the development plan package. Verify in the discussion how this effect existing and post imperviousness of the site and provide a map that matches what is being proposed under the development plan package.


GENERAL COMMENTS:

Please provide a revised Development Plan Package and Drainage Report that addresses the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments.

For any questions or to schedule meetings call me at 837-4929.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
Planning & Development Services Department
05/14/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Revise the site utility drawing to include the following existing utility information:
a. The location and size of water lines, and the location of fire hydrants.
b. The proposed point of connection to the existing public sewer.
c. The locations of any gas lines, communications cables, on-ground junction boxes, and street lights.
d. Any existing or proposed utility easements
Reference: City of Tucson Administrative Manual, Section 2-06.4.8D and Section 107.2.13, IBC 2012.
05/19/2014 RONALD BROWN H/C SITE REVIEW Reqs Change SHEET 2 of 6
1. Provide a large scale detail of all the different types of accessible parking layouts showing all accessible requirements such as dimensioning, markings, signage, grade slope, ramps as required and aisles.
2. As per table 1106.1, only 2 accessible parking spaces are required. The third one shown is optional.
3. At note 21:
a. Delete the reference to COT STC 207 and substitute 2009 ICC A117.1, Section 405.
b. Delete the detectable warning requirement, not required.
END OF REVIEW
05/28/2014 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change UNIFIED DEVELOPMENT CODE

ARTICLE 7: DEVELOPMENT STANDARDS

LANDSCAPING AND SCREENING

Street landscape borders must be located entirely on site, except that, if approved by the City Engineer or designee, up to five feet of the required ten foot width may be placed within the adjacent right-of-way area or within the Major Streets and Routes (MS&R) right-of-way area on MS&R streets. Obtain permission for use of R.O.W or relocate landscape as necessary.

Screening for individual land uses and zones must be provided as determined in Table 7.6.4-1 and in addition to the required landscape borders. Screening is not required between similar uses in accordance with Table 7.6.4-1. A 5' Wall is required to screen parking lot from residential zoning. All required walls must be of masonry material or masonry with a stucco or textured finish.

Interior landscape borders are required as determined in Table 7.6.4-1, which ranks land uses and zones based upon their land use intensity and the impact a use will have on adjacent land uses. Interior landscape borders are required adjacent to residential zones.

ADMINISTRATIVE MANUAL SECTION 2-10.0.0: LANDSCAPE PLAN REQUIREMENTS

Identification and Descriptive Data

All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.

The landscape plan will contain the following identification in the lower right corner of each sheet:

Rezoning case;

Subdivision case;

Board of Adjustment case;

Design Development Option case;

Development Review Board (DRB) case; and/or,
Any other relevant case number for reviews or modifications that affect the site.

Planting Plan

Vegetation Plan and Schedules

Indicate both the proper and common name of each type of plant material, including existing vegetation to remain in place and removed vegetation.

Ensure that all Zoning and Engineering comments and concerns are addressed.

Additional comments may apply
05/28/2014 ANDREW CONNOR NPPO REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/05/2014 CPIERCE1 OUT TO CUSTOMER Completed