Permit Number - DP14-0053
Review Name: RESUB - SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/18/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The rim elevation of the next upstream sanitary manhole (2525.85') is higher than the first floor elevation (2521.50'). Provide a note on the drawing indicating that a backwater valve will be required per Section 715.1, IPC 2012, as amended by the City of Tucson.
2. Revise the site drawing to include the location of any existing fire hydrants. Reference: City of Tucson Administrative Manual, Section 2-06.4.8D and Section 107.2.1, IBC 2012.
06/25/2014 RONALD BROWN HC SITE REVIEW Reqs Change SHEET C4
1. Change the General ADA Site Notes to read General Accessible Site Notes
2. Special Notes:
a. At note 1 change the ADAAG references to 2012 IBC, Chapter 11 and the 2009 ICC A117.1.
b. At note 2 delete all ADAAG references.
c. At note 3 reference comment 2a above
3. Comment: Accessibility for all private projects are governed by the 2012 IBC, Chapter 11 and the 2009 ICC A117.1 as reference under the BUILDING CODE summary on sheet CS-1.0. However, a 2010 ADASAD review is available upon approval of an appeal to the building official. This form is available on our web site and a fee of $132.50 is required. Please coordinate your application with Ms. Angie Ruiz, (520) 837-4896.
4. Revise the ADA NOTE to:
a. Accessible Note
b. Delete the ADAAG reference and replace with 2012 IBC Chapter 11 and the 2009 ICC A117.1.
5. In the uppermost north west corner of the plan there appears to be missing line defining a couple of ramps and also in the same area on sheet C2. Please clearify.
6. Please provide a written response with each review.
END OF REVIEW