Permit Number: DP14-0053
Parcel: 127022690

Address:
5324 E 1ST ST

Review Status: Completed

Review Details: SITE and/or GRADING

Permit Number - DP14-0053
Review Name: SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/10/2014 RBROWN1 ADA REVIEW Passed
04/11/2014 MARTIN BROWN FIRE REVIEW Approved
04/30/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. An approved development plan or an approved grading permit is not to be used for construction of on-site utilities (e.g. water service to buildings, building sewers, site lighting, or electrical service to buildings). The site utility plan shall indicate the locations of future site utilities but all construction notes for the on-site utilities shall be removed from the drawing. The construction of on-site utilities serving a building shall be done as part of a building permit.
2. Coordinate the civil and plumbing plans with respect to the water service for the new kitchen. The civil plan (C3) shows a 1" service pipe connecting to an existing 3" water meter to serve the kitchen as compared to the plumbing plans which call for a new 1" meter, a 1-1/4" RPBP, and a 1-1/4" service pipe.
3. Revise the site drawing to include the following existing utility information:
a. The location of fire hydrants.
b. The location and size of sanitary and storm sewers, including the pipe diameter and the invert and rim elevations of all manholes and cleanouts; along with the Pima County Wastewater Management Department (PCWMD) reference number.
c. The proposed point of connection to the existing public sewer.
Reference: City of Tucson Administrative Manual, Section 2-06.4.8D and Section 107.2.13, IBC 2012.
05/01/2014 ANDREW CONNOR NPPO REVIEW Approved
05/01/2014 ANDREW CONNOR LANDSCAPE REVIEW Approved
05/07/2014 RONALD BROWN H/C SITE REVIEW Reqs Change 1. Please provide a new site plan showing just the building site and hardscape plan without all the utilities and existing Site elements to be demolished.
a. Show the accessible routes, stairs, handrails patios, planters and ramps.
b. Show the connection and make a clear graphic distiction between the existing and new.
2. Provide handrails at the steps as per the 2012 IBC, Sections 1012 and 1012.9 and the 2009 ICC A1771.1, section 504.6 and 505.
a. Provide a handrail elevation as there are none shown in the architectural plans.
b. Provide a stair section showing all dimensions, risers, treads, concrete, foundation and reinforcing as there are none shown on the architectural nor structural plans.
4. Provide a note to the effect that all slopes of the accessible route are to comply with the 2009 ICC A117.1, Section 403.3, 5% maximum running slope and 2% maximum cross slope.
5. Provide a directional arrow for the ramps and a slope percentage.
END OF REVIEW

Final Status

Task End Date Reviewer's Name Type of Review Description
05/13/2014 CPIERCE1 OUT TO CUSTOMER Completed