Permit Number: DP14-0047
Parcel: 141113800

Review Status: Completed

Review Details: RESUB - SITE/GRADING ALL

Permit Number - DP14-0047
Review Name: RESUB - SITE/GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/10/2014 JASON GREEN ENGINEERING REVIEW Approved
06/18/2014 DAVID RIVERA ZONING REVIEW Approved
06/25/2014 RONALD BROWN H/C SITE REVIEW Approved
07/01/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed. Provide the rim elevation of the next upstream sanitary manhole (3953-07). Determine the need for a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson.
2. The minimum size for water service to a building is ¾". Reference: Section 603.1, IPC 2012.
3. An approved development plan is not to be used for construction of on-site utilities (e.g. water service to the building, building sewer, site lighting, or electrical service to the building). The construction of the on-site utilities may be included with the permit for constructing the building or as a separate permit.
07/08/2014 JOE LINVILLE NPPO REVIEW Approved Exception.
07/08/2014 JOE LINVILLE LANDSCAPE REVIEW Approved