Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: DP14-0029
Parcel: 13705168A

Review Status: Completed

Review Details: RESUB - SITE and/or GRADING

Permit Number - DP14-0029
Review Name: RESUB - SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/03/2014 MARTIN BROWN FIRE REVIEW Approved
07/08/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
07/09/2014 ANDREW CONNOR LANDSCAPE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/03/2014 CPIERCE1 APPROVAL SHELF Completed