Permit Number: DP14-0025
Parcel: 13103224R

Address:
5180 E 22ND ST

Review Status: Completed

Review Details: SITE and/or GRADING

Permit Number - DP14-0025
Review Name: SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/20/2014 RONALD BROWN H/C SITE REVIEW Reqs Change SHEET ASP1.1
1. At details 1 and 2
a. Note all new accessible route slopes tom comply with 2009 ICC A117.1, Section 403.3, 5% max running and 2% cross.
b. At note 3.12 change truncated domes to detectable warning strips.
c. Provide dimensions for all accessible parking spaces and aisles.
d. Indicate Van Accessible parking space.
e. Delete all the detectable warning strips in the sidewalk located in front of the four accessible parking spaces, not required.
f. For all ramps show directional arrow and slope percentage.
g. Indicate how access from the accessible parking aisle is achieved to the accessible route, ramp or no ramp?
h. Show accessible signage and provide large scale signage detail including Van Acessible signage.
2. At detail 3 provide a large scale detail of both accessible parking groups and show all accessible requirements such as dimensions, van accessible spaces, signage, grade slopes, ramps and slopes, aisles, and markings.
SHEET ASP1.0
3. Provide a dashed line around the two accessible parking groups that do not have a dashed line and reference to the newly required large scale details as per comment 2a.
END OF REVIEW
02/20/2014 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1. Dumpster enclosure must have bollards along the side walls in addition to the rear walls.
2. Provide dimensions for PAALs and sidewalks and other features on the site plan.
02/20/2014 RBROWN1 ADA REVIEW Passed
02/20/2014 STEVE SHIELDS ZONING REVIEW Needs Review
02/20/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed .
02/20/2014 ANDREW CONNOR LANDSCAPE REVIEW Approv-Cond
02/20/2014 ANDREW CONNOR NPPO REVIEW Approv-Cond
02/20/2014 MARTIN BROWN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/11/2014 FERNE RODRIGUEZ OUT TO CUSTOMER Completed