Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: DP14-0010
Parcel: 125101360

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP14-0010
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/19/2014 CPIERCE1 START PLANS SUBMITTED Completed
03/20/2014 DAVID RIVERA ZONING REVIEW Approved
03/27/2014 PGEHLEN1 COT NON-DSD ENVIRONMENTAL SERVICES Approved Patricia,

Jeff has made the corrections I requested and I can approve the DP once the revised plans are made part of the submittal.

Ken



From: Jeff Behrana [mailto:JBehrana@optimuscdg.com]
Sent: Tuesday, March 18, 2014 10:52 AM
To: 'Ken Perry'; 'David Rivera'
Cc: Patricia.Gehlen@tucsonaz.gov; 'Lisa Bowers'
Subject: RE: mattress Firm



Dear Ken & David,



Per my conversatioopn with Trish, I am trying to secure help from both of you to get our DP signed off so we can get permits.



David R



David, I already took care of your comments last Friday and cleaned up the key note call outs to your satisfaction as per our e-mail correspondence. Trish wanted to be cc so I am reiterating it.. I have updated that sheet accordingly (attached). I will have Lisa Hand carry that sheet for you over the counter once ken signs off on it.



Ken P.



Ken attached are the revised PDF’s for your review and approval based on your comments below and my responses in red



1. Add a note that the gates must not contain a center post for support to Detail 3 on Sheet 5.—Done –keynote #7 under 3/G-1

2. Show the 20 ft. clear dimension required inside the enclosure on Detail 3 on Sheet 5. Done

3. Show the existing bollards as denoted by keynote number 1. Done-

4. Add to the concrete note for the apron that the slab must have rebar reinforcing per Figure 3A in TSM Section 8. Done –keynote # 2 under 3/G-1. I also updated the detail call out on sheet 4(DTl-1) attached

5. The gate cover is noted as 18 ga. steel. Change this to 1/8” steel plate. Done-keynotes 6&7 under 1/G-1 and 2/G-2.



I will send full size with my stamp on it to Lisa, if everyone is Ok per this e-mail



thanks for the assistance .



Ken











Jamsheed (Jeff) D. Behrana, P.E. (AZ, CA & IN)

Managing Partner



Optimus Civil Design and Survey LLC

4650 E. Cotton Center Blvd., Suite 200

Phoenix, Arizona 85040

Office: 602.286.9300

Direct: 602.393.5234

Cell: 602.677.7171

Fax: 602.286.9350

jbehrana@optimuscdg.com

website: www.optimuscdg.com


--------------------------------------------------------------------------------

From: Ken Perry [mailto:kperry@perryengineering.net]
Sent: Tuesday, March 18, 2014 8:27 AM
To: Jeff Behrana
Cc: Patricia.Gehlen@tucsonaz.gov
Subject: RE: mattress Firm



Jeff,

I have taken a look at your resubmittal. There are a few things that need to be addressed. I will send my comments into DSD today.



6. Add a note that the gates must not contain a center post for support to Detail 3 on Sheet 5.

7. Show the 20 ft. clear dimension required inside the enclosure on Detail 3 on Sheet 5.

8. Show the existing bollards as denoted by keynote number 1.

9. Add to the concrete note for the apron that the slab must have rebar reinforcing per Figure 3A in TSM Section 8.

10. The gate cover is noted as 18 ga. steel. Change this to 1/8” steel plate.

Ken
03/27/2014 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Approved