Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: DP13-0253
Parcel: 117060670

Address:
220 N 4TH AV

Review Status: Active

Review Details: RESUB - SITE and/or GRADING

Permit Number - DP13-0253
Review Name: RESUB - SITE and/or GRADING
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
08/11/2014 MARTIN BROWN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/11/2014 CPIERCE1 APPROVAL SHELF RECEIVED