Permit Number: DP13-0234
Parcel: 13014005A

Review Status: Completed

Review Details: SITE and/or GRADING

Permit Number - DP13-0234
Review Name: SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/27/2013 RBROWN1 ADA REVIEW Passed
12/02/2013 KEN BROUILLETTE FIRE REVIEW Approved
12/17/2013 RONALD BROWN H/C SITE REVIEW Approved
12/20/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the site drawing to include the following information:
a. The pipe diameter of the public sanitary sewer, the invert and rim elevations of all manholes; and the Pima County Wastewater Management Department (PCWMD) reference number for each manhole.
b. The first floor elevation for the building
Reference: City of Tucson Administrative Manual No. 2-06.0.0, Section 4.8 and Section 107.2.13, IBC 2012.
2. Coordinate the sizes of the water service from the meter to the building with the plumbing design on sheet P-1.
12/24/2013 JOE LINVILLE NPPO REVIEW Passed
12/24/2013 JOE LINVILLE LANDSCAPE REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
01/08/2014 CPIERCE1 REJECT SHELF Completed