Permit Number: DP13-0223
Parcel: 12314138C

Review Status: Completed

Review Details: RESUB - SITE/GRADING ALL

Permit Number - DP13-0223
Review Name: RESUB - SITE/GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/24/2014 KEN BROUILLETTE FIRE REVIEW Approved
03/24/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide rim elevation of upstream cleanout. [Initial comment: Provide the rim elevation of the next upstream sanitary manhole or cleanout. Determine the need for any backwater valves per Section 715.1, IPC 2012, as amended by the City of Tucson.]
2. Provide a ¾" meter for each 6-bedroom unit. [Initial comment: Tucson Water limits the demand flow through a 5/8" water meter to a maximum of 15 GPM. Based on the assumptions noted in item 3, the 5/8" water meters will be too small for the intended use. Basis: Table E103.3(2), 2012 IPC.]
3. Provide note on drawing. [Initial comment: How will water be supplied to the pool?]
03/24/2014 RONALD BROWN H/C SITE REVIEW Approved
03/27/2014 SPOWELL1 LANDSCAPE REVIEW Needs Review
03/27/2014 SPOWELL1 ZONING REVIEW Needs Review
03/27/2014 SPOWELL1 ENGINEERING REVIEW Needs Review