Permit Review Detail
Review Status: Completed
Review Details: RESUB - SITE/GRADING ALL
Permit Number - DP13-0223
Review Name: RESUB - SITE/GRADING ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/24/2014 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 03/24/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide rim elevation of upstream cleanout. [Initial comment: Provide the rim elevation of the next upstream sanitary manhole or cleanout. Determine the need for any backwater valves per Section 715.1, IPC 2012, as amended by the City of Tucson.] 2. Provide a ¾" meter for each 6-bedroom unit. [Initial comment: Tucson Water limits the demand flow through a 5/8" water meter to a maximum of 15 GPM. Based on the assumptions noted in item 3, the 5/8" water meters will be too small for the intended use. Basis: Table E103.3(2), 2012 IPC.] 3. Provide note on drawing. [Initial comment: How will water be supplied to the pool?] |
| 03/24/2014 | RONALD BROWN | H/C SITE | REVIEW | Approved | |
| 03/27/2014 | SPOWELL1 | LANDSCAPE | REVIEW | Needs Review | |
| 03/27/2014 | SPOWELL1 | ZONING | REVIEW | Needs Review | |
| 03/27/2014 | SPOWELL1 | ENGINEERING | REVIEW | Needs Review |