Permit Review Detail
Review Status: Completed
Review Details: DEV PKG - RESUBMITTAL
Permit Number - DP13-0221
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/21/2014 | CPIERCE1 | START | PLANS SUBMITTED | Completed | |
| 06/03/2014 | PATRICIA GEHLEN | ZONING-DECISION LETTER | REVIEW | Reqs Change | This review has been completed and resubmittal is required. The following items need to be resubmitted: 1) Two rolled sets of the plans 2) A disk containing all items submitted. 3) All items requested by review staff 4) All items needed to approve these plans |
| 06/03/2014 | PGEHLEN1 | ENV SVCS | REVIEW | Reqs Change | The resubmittal has been reviewed on behalf of ESD and is conditionally approved pending the following revisions: 1. The enclosure must be constructed per the minimum requirements as shown in Figure 3B in TSM Section 8. Either delete the conflicting call outs on the enclosure detail shown on Sheet C2 and add that the enclosure and apron will be constructed per Figure 3B, or add the appropriate notes. The concrete slab and apron/ramp require reinforcing rebar per the detail. The doors must be constructed of at least 1/8” thick steel, and the hinges must be per the details. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/19/2014 | PGEHLEN1 | APPROVAL SHELF | Completed |
| 06/19/2014 | PGEHLEN1 | OUT TO CUSTOMER | Completed |
| 06/19/2014 | CPIERCE1 | REJECT SHELF | Completed |