Permit Number: DP13-0207
Parcel: 12711069A

Review Status: Completed

Review Details: RESUB - SITE and/or GRADING

Permit Number - DP13-0207
Review Name: RESUB - SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/22/2014 DAVID RIVERA ZONING REVIEW Approved
02/03/2014 RONALD BROWN HC SITE REVIEW Reqs Change ALL RESUBMITTAL COMMENTS ARE PRESENTED IN ALL CAPS

SHEET 2
1. OK
2. Provide 1 "Van Accessible" parking space. Include a large scale detail showing all accessibility requirements.
THIS IS A SELF SERVICE CAR WASH. ALL VACCUUM PARKING SPACES ARE PUBLIC PARKING. PLEASE PROVIDE ONE VAN ACCESSIBLE VACCUUM PARKING SPACE WITH AN AISLE CONNECTED TO THE ACCESSIBLE ROUTE TO THE SPEEDWAY RIGHT OF WAY.

3. A building permit will be required for the new canopies. Code requires a 1 hour fire separation rcmu fence between the new canopy that is within 10' of the property line, 2012 IBC, Table 602.
PLEASE SHOW THE FENCE ALONG THE ENTIRE LENGTH OF THE CANOPY AND NOTE THE FIRE RATING AS REQUIRED BY CODE. CONSTRUCTION DETAILS MAY BE SUBMITTED WITH CANOPY CONSTRUCTION PERMIT.

SHEET 4
4. OK
5. At detail "D":
a. Change the 1:10 slope of the ramps to 1:12 maximum.
b. Add a note requiring 5% maximum running slope at the marked crossing.
IF FLARED SIDES OF THE CURB RAMP ARE RETAINED, PROVIDE A 1:10 MAXIMUM SLOPE AS PER 2009 ICC A117.1, SECTION 406.7.

END OF RESUBMITTAL REVIEW
02/03/2014 ANDREW CONNOR LANDSCAPE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/07/2014 SHANAE POWELL OUT TO CUSTOMER Completed
03/07/2014 SHANAE POWELL REJECT SHELF Completed