Permit Number: DP13-0205
Parcel: 12412078A

Address:
124 S CHERRY AV

Review Status: Completed

Review Details: TENTATIVE PLAT REVIEW

Permit Number - DP13-0205
Review Name: TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/18/2013 SPOWELL1 START PLANS SUBMITTED Completed
10/21/2013 RONALD BROWN ADA REVIEW Passed
10/22/2013 ROBERT YOUNG PIMA COUNTY PIMA CTY - DEV REVIEW Passed Patricia,

I just received direction from my manager that future reviews should be directed to PC DOT's Traffic Engineering Division. Mo Farhat and Lauren Maine would be your primary contacts. They can be reached at 740-2601.

However, I can guarantee the South Cherry Residential Tentative Plat (DP13-0205) will not need their review, so our folder can be closed out.

I apologize for the confusion. We have undergone some recent restructuring, and this was an item I needed to get clarity on.

Sincerely,
Jessica Orto
Pima County Building and Site Development
520.724.6490
10/22/2013 PGEHLEN1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Approved See letter in SIRE
10/23/2013 PGEHLEN1 UTILITIES SOUTHWEST GAS Approved Letter and additional information is in SIRE. Letter contains informational information only.
10/24/2013 MARTIN BROWN COT NON-DSD FIRE Denied Please indicate location)s) of existing and/or proposed fire hydrants. Refer to chapter 5 of the 2013 IFC for spacing requirements.
Please indicate proposed use of buildings. Indicate if fire sprinklers will be installed.
10/25/2013 STEVE SHIELDS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: South Cherry Residential
Development Package (1st Review)
DP13-0205

TRANSMITTAL DATE: October 28, 2013

DUE DATE: November 18, 2013

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

The review comments include the actual standard first with the applicable Administrative Manual section number and the following paragraph is the actual comment related to the specific item that must be addressed. If you need to review the sections listed below click on the link or copy it in the address bar of your internet program. http://www.amlegal.com/nxt/gateway.dll/Arizona/tucson_az_udc/administrativemanual?f=templates$fn=default.htm$3.0$vid=amlegal:tucson_udc_az

This link will take you directly to the section used for the standards review. The UDC & TSM requirements are in the Unified Development Code and can be viewed at the same web link as above

1. Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is October 19, 2014 .

2-06.4.0 CONTENT REQUIREMENTS

2-06.4.3 - The administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet.

1. COMMENT: Provide the development package case number, DP13-0205, adjacent to the title block on all sheets.

2. COMMENT: Clarify why development package case number, DP12-0209, is listed on this plan. If this plan is no longer valid with drawn the plan.
2-06.4.7.A.4 - Identify the existing and proposed use of the property as classified per the UDC. List all UDC sections applicable to the proposed uses.

3. COMMENT: It appears that there are three primary uses proposed for this site, multi-family, parking & commercial recreation (pool). Clarify what is happening on this site. If the parking and pool are strictly for the multi-family units clearly demonstrate how all will function, i.e. CC&Rs, how will the parking and pool be maintained etc. Should the parking and pool be common areas?

2-06.4.7.A.8.b - Percentage and area in square feet of building and accessory building coverage;

4. COMMENT: Provide a lot coverage calculation the includes the allowed and proposed lot coverage for each lot, see UDC Section 6.4.3.

2-06.4.8.C - The following information regarding existing private or public right-of-way adjacent to or within the site shall be provided: the name, right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts, and sidewalks.

5. COMMENT: Provide a dimension from centerline of street to curb and curb to property line for both Cherry & 12th.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

2-06.4.9.B - Identify each block or lot by number within the subdivision boundary and include the approximate square footage of each, or a note may be provided stating that all lots comply with the minimum lot size requirements.

6. COMMENT: Identify each lot by number within the subdivision boundary and include the approximate square footage of each.

2-06.4.9.C - If the project has common areas, label each common area individually with a separate letter designation. Enclose with a solid line each common area, private street, etc., that will have separate restrictions, a separate homeowners' association, or any common area that is separated by a public right-of-way.

7. COMMENT: Depending on how comment 3 above is addressed the above information may be required.

2-06.4.9.H.5.a - Show all motor vehicle off-street parking spaces provided, fully dimensioned. As a note, provide calculations on the number of spaces required (include the ratio used) and the number provided, including the number of spaces required and provided for the physically disabled. The drawing should indicate parking space locations for the physically disabled. A typical parking space detail shall be provided for both standard parking spaces and those for the physically disabled. For information on parking requirements for the physically disabled, refer to adopted building and accessibility codes of the City of Tucson. Design criteria for parking spaces and access are located in Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC.

8. COMMENT: Provide a typical parking space detail for both standard parking spaces and those for the physically disabled.

2-06.4.9.H.5.d - Show bicycle parking facilities fully dimensioned. For specifics, refer to Section 7.4.9, Bicycle Parking Design Criteria, of the UDC. Provide, as a note, calculations for short and long term bicycle spaces required and provided.

9. COMMENT: The required number of short term bicycle parking spaces shown is not correct. Per UDC Section 7.4.3.G Fractional Amounts. When the calculation of required motor vehicle and bicycle parking spaces results in a fractional number, a fraction of one-half or more is adjusted to the next higher whole number, and a fraction of less than one-half is adjusted to the next lower whole number. That said 24 x 0.1 = 2.4 or 2 required.

10. COMMENT: Detail F" sheet 3 is not correct. Review UDC figure 7.4.9-C and revise the detail.

11. COMMENT: The proposed short-term bicycle parking does not meet the requirements of UDC Sections 7.4.9.C.a & d.

2-06.4.9.O - All applicable building setback lines, such as erosion hazard, floodplain detention/retention basins, and zoning, including sight visibility triangles, will be shown.

12. COMMENT: As you have proposed individual residence on individual lots the interior perimeter yard setbacks will be based on a "Res Use" to a "Nonres Zone" having a 10' or 3/4 (H) of the building exterior wall, which ever is greatest. Based on a wall height of 18' the required interior perimeter yard setback would be 13.5'. All proposed buildings have interior perimeter yard setback issues. A Design Development Option (DDO) will need to be approved for each residence on each lot prior to approval of this development package.

2-06.4.9.T - Show refuse collection areas, including locations of dumpsters, screening location and materials, and vehicle maneuverability, fully dimensioned, and access route. If dumpster service is not proposed, indicate type of service. For specific information on refuse collection, refer to Section 8-01.0.0, Solid Waste and Recycle Disposal, Collection, and Storage, of the Technical Standards Manual. Refuse collection on all projects shall be designed based on that section, even if collection is to be contracted to a private firm.

COMMENT: Show the refuse collection area on the plan.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
.
10/28/2013 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved Regional Traffic Engineering has no comments on this submittal and supports its approval. Thank you.

________________________________

Confidentiality and Nondisclosure Notice: This email transmission and any attachments are intended for use by the person(s)/entity(ies) named above and may contain confidential/privileged information. Any unauthorized use, disclosure or distribution is strictly prohibited. If you are not the intended recipient, please contact the sender by email, and delete or destroy all copies plus attachments.
.
10/29/2013 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved 4350 E. Irvington Road, Tucson, AZ 85714
Post Office Box 711, Tucson, AZ 85702

WR#269945 October 29, 2013

Cypress Civil Development
Attn: Kevin M. Hall
2102 N Country Club Suite 9
Tucson, Arizona 85716


Dear Kevin M. Hall:


SUBJECT: South Cherry Residential Tentative Plat
DP13-0205

Tucson Electric Power Company has reviewed and approved the development plan submitted October 28, 2013. It appears that there are no conflicts with the existing facilities within the boundaries of this proposed development.

Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities. Any relocation costs will be billable to the customer.

In order to apply for electric service, call the New Construction Department at (520) 918-8300. Submit a final set of plans including approved site, electrical load, paving off-site improvements and irrigation plans, if available include a CD with the AutoCAD version of the plans.

If easements are required, they will be secured by separate instrument. Your final plans should be sent to:
Tucson Electric Power Company
Attn: Mr. Richard Harrington
New Business Project Manager
P. O. Box 711 (OH-204)
Tucson, AZ 85702
520-917-8726

Should you have any technical questions, please call the area Designer Mike Kaiser at (520) 918-8244.
Sincerely,


Tina Zarate
Office Support
Design/Build
Enclosures
cc: DSD_CDRC@tucsonaz.gov, City of Tucson (email)
M. Kaiser, Tucson Electric Power
10/29/2013 PGEHLEN1 PIMA COUNTY WASTEWATER Denied PIMA COUNTY
REGIONAL WASTEWATER RECLAMATION DEPARTMENT
201 NORTH STONE AVENUE
TUCSON, ARIZONA 85701-1207
JACKSON JENKINS PH: (520) 740-6500
DIRECTOR FAX: (520) 620-0135


October 29, 2013


To: KEVIN M. HALL, P.E.
CYPRESS CIVIL DEVELOPMENT, INC.

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department


____________________________________________
From: Tom Porter, P.E. (520-740-6719), Pima County Regional Wastewater Reclamation Department

Subject: SOUTH CHERRY RESIDENTIAL
Development Plan - 1st submittal
DP13-0205

The Pima County Regional Wastewater Reclamation Department (PCRWRD) has reviewed the proposed sewer collection lines for the above-referenced project. The following comments are offered for your use:

The Pima County Regional Wastewater Reclamation Department hereby conditionally approves the above referenced submittal of the Development Plan with the following conditions:

1. The Type II obtained for the previous project is no longer valid because you have changed the connection point and possible GPD for the new use. Obtain a letter from the PCRWRD's Development Liaison Unit, written within the past year, stating that treatment and conveyance system capacity for the project is available in the downstream public sewerage system and provide a copy of that letter to this office. The required form to request such a letter may be found at:

http://www.pima.gov/wwm/developer.htm#permits

The development plan for this project cannot be approved until a copy of this letter has been received by this office.

2. Sheet 1: The 204 FUE shown in General Note #9 seems low and may need to be revised for the proposed buildings shown on plan.
The corrections can be shown by PDF or Mylar. The revised Type II letter can be sent to me by e-mail and an approval letter will be sent upon completion.
10/30/2013 PGEHLEN1 PIMA COUNTY ADDRESSING Denied MICHELENE NOWAK
ADDRESSING REVIEW
PH #: 724-9512

TO:

CITY PLANNING

FROM:

MICHELENE NOWAK, ADDRESSING REVIEW

SUBJECT:

DP13-0205/SOUTH CHERRY RESIDENTIAL-TENTATIVE PLAT 1ST REVIEW

DATE:

OCTOBER 30, 2013




The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

1. Label Project# DP13-0205 on all Sheets

2. Remove "Addition" from legal of University Heights Mp 3 Pg 102 on all Sheets

3. For 911 purposes the current Address of 124 S Cherry Av will change due to no physical access to Cherry Av (per Tentative Plat) Access for project is: 12th Street

4. Provide site plan for the 6 --2 story buildings (6 Buildings) showing unit numbering scheme in accordance with county standards
11/05/2013 ED ABRIGO PIMA COUNTY ASSESSOR Approved Office of the Pima County Assessor
115 N. Church Ave.
Tucson, Arizona 85701

BILL STAPLES
ASSESSOR




TO: CDRC Office
Subdivision Review
City of Tucson (FAX# 791-5559)



FROM: Susan King
GIS Cartographer
Pima County Assessor's Office


DATE: November 5, 2013


RE: Assessor's Review and Comments Regarding Tentative Plat
DP13-0205 South Cherry Residential

* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

X Plat meets Assessor's Office requirements.
_______ Plat does not meet Assessor's Office requirements.

COMMENTS:

NOTE: THE ASSESSOR'S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED.

Thank you,

Susan King
11/06/2013 ZELIN CANCHOLA COT NON-DSD TRAFFIC Denied From Zelin Canchola
TDOT
DP13-0205 124 S Cherry Av
November 6, 2013

Revise driveway design with 18 feet curb return radius.
11/13/2013 PGEHLEN1 POLICE REVIEW Approved I have no issues with this request.

CSO Becky Noel #37968
Tucson Police Dept
837-7428
11/13/2013 PGEHLEN1 OTHER AGENCIES PIMA ASSN OF GOVTS Approved Here are my comments -

DATE: 11/12/2013
CASE: DP13-0205 SOUTH CHERRY RESIDENTIAL - TENTATIVE PLAT
COMMENT: No objections or adverse comments

Daily PM Peak
Vehicle Trip Generation: 0 4

Thanks,
-Eric

Additional notes:

See additional information in SIRE
11/13/2013 JOHN BEALL COT NON-DSD COMMUNITY PLANNING Passed
11/14/2013 RONALD BROWN H/C SITE REVIEW Denied 1. Add the following to note 11, "All accessible routes are to comply with 2009 ICC A117.1, Section 403.3; 5% maximum running slopes and 2% maxium cross slopes".
2. Show accessibility to all common areas, pools etc.
3. Show the slopes at both accessible parking ramps to be 1:12 maximum.
END OF REVIEW
11/18/2013 PGEHLEN1 ENV SVCS REVIEW Denied 1. Show how solid waste and recycling will be provided for the multi-family project per TSM Section 8. There does not appear to be any enclosure locations shown, nor dimensions or construction details for the container enclosure(s) on the plans.

2. Per TSM 8-01.4.B, add the general note specifying anticipated method of collection and frequency.

3. There may be additional comments once the solid waste and recycling provisions are provided on the plans.

If there are questions, I can be contacted at kperry@perryengineering.net
11/18/2013 JANE DUARTE COT NON-DSD PARKS & RECREATION Approved
11/18/2013 JOE LINVILLE LANDSCAPE REVIEW Approved
11/18/2013 LOREN MAKUS ENGINEERING REVIEW Denied Show grade break in the parking area and provide sufficient detail for construction and inspection.
Delineate and describe the water harvesting areas. Show spot grades throughout the site to demonstrate the run-off will be directed toward the water harvesting to the maximum extent practicable.
11/18/2013 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Approved
11/19/2013 PGEHLEN1 OTHER AGENCIES TUCSON AIRPORT AUTHORITY Passed
11/19/2013 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Reqs Change This review has been completed and resubmittal is required. Please resubmit the following:

1) Two rolled sets of the plans
2) One disk containing all items submitted
3) All items requested by review staff
4) All items needed to approve the plans.
11/19/2013 PGEHLEN1 OTHER AGENCIES U. S. POST OFFICE Passed
11/19/2013 PGEHLEN1 UTILITIES EL PASO NATURAL GAS Passed
11/19/2013 PGEHLEN1 UTILITIES CENTURYLINK Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
02/25/2014 CPIERCE1 OUT TO CUSTOMER Completed
02/25/2014 CPIERCE1 REJECT SHELF Completed