Permit Number: DP13-0158
Parcel: 132130750

Address:
3350 S PARK AV

Review Status: Completed

Review Details: GRADING

Permit Number - DP13-0158
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/17/2013 ANDREW CONNOR NPPO REVIEW Reqs Change The grading plan has been reviewed by the Landscape / NPPO Section but cannot approve the plan until all Engineering, comments, concerns, and appropriate revisions have been addressed
09/18/2013 STEVE SHIELDS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Planning and Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: The Bridges - Block 10
Grading Plan (1st Review)
DP13-0158

TRANSMITTAL DATE: September 18, 2013

GRADING PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Unified Development Code (UDC), Administrative Manual (AM) & Technical Standards Manual (TSM) were addressed.

1. This grading was reviewed for compliance with the approved development package/tentative plat.

2. The grading plan is in substantial compliance with the approved development package/tentative plat. Once Engineering and Landscape have approved Zoning will approve.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

Sshield1 on DS1/planning/New Development Package/ DP13-0158

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package.
09/18/2013 ELIZABETH EBERBACH ENGINEERING REVIEW Denied DATE: September 18, 2013
FOR: Pat Marum, P.E., Wood Patel Engineering
SUBJECT: The Bridges Block 10 S11-043 Grading Plan Engineering Review
LOCATION: T14S R14E Section 30
REVIEWER: Elizabeth Leibold
ACTIVITY NUMBER: DP13-0158

SUMMARY: Engineering has reviewed the development package, and does not recommend approval until the following comments are addressed.

MASTER COVER SHEETS/ GENERAL NOTES/GRADING SHEET COMMENTS:
1) Admin Man Sec.2-06.3.5: Add Development Package stamp to all sheets. http://cms3.tucsonaz.gov/sites/default/files/dsd/CDRC/dvpkg_stamp_10-11.jpeg
2) Admin Man Sec.4.9.S: See redline comments. Return redlines with resubmittal.
3) Tech Man Sec.4-04.9.3: Provide geotechnical supporting documentation for north slope - rear lot walls appear to abut slope that is adjacent to north swale. Verify setback.
4) Admin Man Sec.4.9.N.1: Provide WSEL's along north channel and within basin limits. Add WSEL data to both plan view and cross sections on sheet 4.
5) Tech Man Sec.4-04: Provide velocity in north channel / explain why erosion protection is not provided. Also identify Q100 within north channel.
6) Tech Man Sec.4-04: Provide at minimum one 15-ft wide maintenance access ramp that may be used concurrently with other access ramps. Also identify material for stabilization for each ramp.
7) Tech Man Sec.4-03.4.3: Provide computation and clarification of Cedar Creek Street capacity assuming full imperviousness cover for Block A.
8) Tech Man Sec.2-01.9: Label Grading limits on cross section details on sheet 4.
9) Tech Man Sec.4-03.3.3.4: Provide unattenuated flow condition erosion protection along basin 'entrance' area of constructed slopes.
10) Tech Man Sec.2-01: Label total disturbance area on cover sheet.
11) Tech Man Sec.2-01.4: Identify and label local benchmark with datum on planview.

If you have any questions, please call me at 837-4934.

Elizabeth Leibold, P.E., CPM, CFM
Civil Engineer
Engineering Division
Planning & Development Services

Final Status

Task End Date Reviewer's Name Type of Review Description
10/02/2013 CPIERCE1 REJECT SHELF Completed