Permit Review Detail
Review Status: Active
Review Details: SITE and/or GRADING
Permit Number - DP13-0144
Review Name: SITE and/or GRADING
Review Status: Active
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/05/2013 | CARL SCHULTZ | FIRE | REVIEW | Approved | |
09/05/2013 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
09/05/2013 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
09/05/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | The rim elevation of the next upstream sanitary manhole (45.53') is less than 12" below the first floor elevation (46.35'). Provide a note requiring the installation of a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/05/2013 | ANY | APPROVAL SHELF | RECEIVED |