Permit Number: DP13-0144
Parcel: 11901042B

Address:
200 E BENSON HY

Review Status: Active

Review Details: SITE and/or GRADING

Permit Number - DP13-0144
Review Name: SITE and/or GRADING
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
09/05/2013 CARL SCHULTZ FIRE REVIEW Approved
09/05/2013 LOREN MAKUS ENGINEERING REVIEW Approved
09/05/2013 STEVE SHIELDS ZONING REVIEW Approved
09/05/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved The rim elevation of the next upstream sanitary manhole (45.53') is less than 12" below the first floor elevation (46.35'). Provide a note requiring the installation of a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/05/2013 ANY APPROVAL SHELF RECEIVED