Permit Number: DP13-0143
Parcel: 129080050

Address:
1665 E 22ND ST

Review Status: Completed

Review Details: SITE and/or GRADING

Permit Number - DP13-0143
Review Name: SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2013 STEVE SHIELDS ZONING REVIEW Approved
08/02/2013 JASON GREEN ENGINEERING REVIEW Needs Review
08/05/2013 RBROWN1 ADA REVIEW Passed
08/05/2013 RONALD BROWN H/C SITE REVIEW Approved Approval is for accessibility within the property boundary lines only. Any right of way modifications and requirements are to be reviewed by COT Department of Transporation.
08/06/2013 ANDREW CONNOR LANDSCAPE REVIEW Approved
08/06/2013 ANDREW CONNOR NPPO REVIEW Approved
08/07/2013 MARTIN BROWN FIRE REVIEW Denied Width of rolling gate shown as 32' on sheet C01, 24' on preliminary layout sheet. Please clarify.
Add notes indicating new access gates will comply with section 503.5 of 2012 IFC.
Proof of current annual sprinkler inspection will be required before final fire inspection.
Indicate location of fire department approved lock boxes to be installed (gate, fire riser room, front door.
08/08/2013 CPIERCE1 PLUMBING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/08/2013 CPIERCE1 OUT TO CUSTOMER Completed