Permit Review Detail
Review Status: Completed
Review Details: SITE and/or GRADING
Permit Number - DP13-0136
Review Name: SITE and/or GRADING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/26/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 07/26/2013 | RBROWN1 | ADA | REVIEW | Passed | |
| 07/29/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Revise the site drawing to include the rim elevation of the upstream manhole. Reference: City of Tucson Administrative Manual No. 2-06.0.0, Section 4.8 and Section 107.2.13, IBC 2012. |
| 07/30/2013 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 08/14/2013 | RONALD BROWN | H/C SITE | REVIEW | Denied | SHEET C3.0 1. The marked crossing to Wilmont does not work. Please relocate to provide a direct connection to the existing Wilmont pedestrian way, not to a concrete drive apron. 2. If the 7.5' wide stripped asphalt paving just West of the existing building is a passenger loading zone, please provide accessible passenger zones as required by the 2012 IBC, Section 1106.7 and ICC A117.1, Section 503. 3. Reference the accessible parking layout and note 17 to detail 2/C6.0. 4. Reference note 18 to detail 5/C6.0. 5. Reference note 23 to detail 6/C6.0. 6. Include a general note that all accessible route slopes are to comply with the ICC A117.1, Section 403.3; 5% maximum running slope and 2% maximum cross slopes. 7. Please identify the four circles within a circle just east of the existing concrete drive apron. Are these bollards? END OF REVIEW |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/20/2013 | CPIERCE1 | REJECT SHELF | Completed |