Permit Number: DP13-0124
Parcel: 13327001B

Review Status: Completed

Review Details: RESUB - SITE and/or GRADING

Permit Number - DP13-0124
Review Name: RESUB - SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/04/2013 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera Principal Planner
for Terry Stevens Lead Planner

PROJECT: DP13-0124
7910 E. Speedway Blvd.
Development Package

TRANSMITTAL DATE: 12/04/2013

COMMENTS: The remaining zoning comments are minor and zoning is willing to review the requested changes and approve the DP over the counter with an appointment. If the applicant wishes to do so please call or email me in advance for an appointment. This is assuming that all other agencies approve the plan and a subsequent submittal of the DP is not required.

1. AM 2-06.4.2 - The title block shall include the following information and be provided on each sheet:

COMMENT: The title block on the landscape sheet must match the title block on the DP sheets. Revise the title block as requested.

2. AM 2-06.4.2.D - The page number and the total number of pages in the package (i.e., sheet xx of xx).

COMMENT: The landscape sheet must include the sheet number 6 of 6. Revise as requested.


If you have any questions about this transmittal, please call David Rivera, (520) 837-4957
12/12/2013 RONALD BROWN HC SITE REVIEW Reqs Change SHEET 3
1. At note 16 add the following: "or 406 as applicable".
2. Add a new note: "All slopes of accessible routes and marked crossings are to comply with ICC A117.1, Section 403.3; 5% maxium running slopes and 2% maximum cross slopes".
SHEET 5
3. At detail B: provide a "Van Accessible" sign just below the accessible parking sign.
4. At detail E: substitute "Accessible Route" in lieu of "ADA".
5. At detail K: Substitute "Accessible" for the term "Handicap".
END OF REVIEW
12/19/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The rim elevation of the next upstream sanitary manhole (2594) is higher than the first floor elevation (2591.50). Note that a backwater valve will be required per Section 715.1, IPC 2012, as amended by the City of Tucson.
12/23/2013 LAITH ALSHAMI ENGINEERING REVIEW Approved Laith Alshami, Engineering and Floodplain Review, 12/23/2013,

SUBJECT: Speedway Pantano Square
DP13-00124, T14S, R15E, SECTION 9

RECEIVED: Development Package and Drainage Report on November 26 10, 2013


The subject project has been reviewed. The Drainage Report and the Development Package are both acceptable. They are recommended for approval pertaining to Engineering and Floodplain Review.

If you have any questions, I can be reached at 837-4933 or Laith.Alshami@tucsonaz.gov
12/24/2013 JOE LINVILLE LANDSCAPE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/14/2014 CPIERCE1 REJECT SHELF Completed