Permit Review Detail
Review Status: Completed
Review Details: RESUB - SITE and/or GRADING
Permit Number - DP13-0124
Review Name: RESUB - SITE and/or GRADING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/04/2013 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | FROM: David Rivera Principal Planner for Terry Stevens Lead Planner PROJECT: DP13-0124 7910 E. Speedway Blvd. Development Package TRANSMITTAL DATE: 12/04/2013 COMMENTS: The remaining zoning comments are minor and zoning is willing to review the requested changes and approve the DP over the counter with an appointment. If the applicant wishes to do so please call or email me in advance for an appointment. This is assuming that all other agencies approve the plan and a subsequent submittal of the DP is not required. 1. AM 2-06.4.2 - The title block shall include the following information and be provided on each sheet: COMMENT: The title block on the landscape sheet must match the title block on the DP sheets. Revise the title block as requested. 2. AM 2-06.4.2.D - The page number and the total number of pages in the package (i.e., sheet xx of xx). COMMENT: The landscape sheet must include the sheet number 6 of 6. Revise as requested. If you have any questions about this transmittal, please call David Rivera, (520) 837-4957 |
| 12/12/2013 | RONALD BROWN | HC SITE | REVIEW | Reqs Change | SHEET 3 1. At note 16 add the following: "or 406 as applicable". 2. Add a new note: "All slopes of accessible routes and marked crossings are to comply with ICC A117.1, Section 403.3; 5% maxium running slopes and 2% maximum cross slopes". SHEET 5 3. At detail B: provide a "Van Accessible" sign just below the accessible parking sign. 4. At detail E: substitute "Accessible Route" in lieu of "ADA". 5. At detail K: Substitute "Accessible" for the term "Handicap". END OF REVIEW |
| 12/19/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The rim elevation of the next upstream sanitary manhole (2594) is higher than the first floor elevation (2591.50). Note that a backwater valve will be required per Section 715.1, IPC 2012, as amended by the City of Tucson. |
| 12/23/2013 | LAITH ALSHAMI | ENGINEERING | REVIEW | Approved | Laith Alshami, Engineering and Floodplain Review, 12/23/2013, SUBJECT: Speedway Pantano Square DP13-00124, T14S, R15E, SECTION 9 RECEIVED: Development Package and Drainage Report on November 26 10, 2013 The subject project has been reviewed. The Drainage Report and the Development Package are both acceptable. They are recommended for approval pertaining to Engineering and Floodplain Review. If you have any questions, I can be reached at 837-4933 or Laith.Alshami@tucsonaz.gov |
| 12/24/2013 | JOE LINVILLE | LANDSCAPE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/14/2014 | CPIERCE1 | REJECT SHELF | Completed |