Permit Number - DP13-0120
Review Name: GRADING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/23/2013 | ELIZABETH LEIBOLD | ENGINEERING | REVIEW | Denied | 1) Floodplain Use Permits for elevation certificates for both proposed equipment pads are required for this project (Phase II of CAVSARP WTP at Mile Wide). Submit applications with resubmittal for DP13-0120 & T13CM03957. 2) Revise detail 5 on sheet C201 to correct callout for dimensions of toedown depth. 3) Add note to sheet C200 that any areas of disturbance for Phase II shall be revegetated with approved seed mix or covered with sized gravel. Final Site Stabilization Note 1 is not accepted; revise. 4) Grading limits shall be clarified on civil plan view sheets including SWPP exhibit, to include all interim SWPP controls, lay down area, and disturbance areas, located within the parcel. Clarify any temporary construction easements if needed. Add delineation line type for grading limits to legend. Call E Leibold P.E., CPM, CFM if you have questions, 837-4934. |
| 07/29/2013 | ANDREW CONNOR | NPPO | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/07/2013 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 08/07/2013 | CPIERCE1 | REJECT SHELF | Completed |