Permit Number: DP13-0115
Parcel: 12217276E

Review Status: Completed

Review Details: SITE and/or GRADING

Permit Number - DP13-0115
Review Name: SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/08/2013 RBROWN1 ADA REVIEW Passed
07/09/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/10/2013 MARTIN BROWN FIRE REVIEW Approved
07/12/2013 STEVE SHIELDS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Planning and Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: Loft Cinema
Development Package (1st Review)
DP13-0115

TRANSMITTAL DATE: July 16, 2013

DEVELOPMENT PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Unified Development Code (UDC), Administrative Manual (AM) & Technical Standards Manual (TSM) were addressed.

1. This site was reviewed for full code compliance for the entire site.

The following comments are based on the requirements of Administrative Manual (AM) 2-06.0. Development package review comments;

1. A.M. 2-06.4.7.A.4 Revise General Note 3 to include "SUBJECT TO USE SPECIFIC STANDARDS 4.9.4.K.1, .2, .3, .4, 4.9.4.C.3, AND 4.9.13.E and 4.9.13.P".

2. A.M. 2-06.4.9.E As this project is comprised of four (4) parcels, 122-17-276E, 122-17-278B, 122-17-283C & 122-17-2820 a lot combination is required. Provide a copy of the approved Pima County Combo Request form with the next submittal.

3. A.M. 2-06.4.9.H Provide fully dimensioned parking area for the entire site. This includes all radii for back-up spurs shown on the plan.

4. A.M. 2-06.4.9.H.a Provide a standard vehicle parking space detail.

5. A.M. 2-06.4.9.H.a On the plan there are to be accessible parking signs shown, Keynote 12 between the accessible vehicle parking spaces and the sidewalk. Show the signs on the "HANDICAP PARKING DETAIL" and provide a dimension that shows that the minimum four (4) sidewalk width is maintained.

6. A.M. 2-06.4.9.H.a Provide a wheel stop location dimension on the accessible and standard vehicle parking space details, see UDC Section 7.4.6.H.3.


7. A.M. 2-06.4.9.H.d Keynote 20, short-term bicycle parking, points to an area that is within a required landscape buffer and a sight visibility triangle and it does not appear to show the twenty (20) short-term bicycle parking spaces. Cleary show the location of the required Short-Term bicycle parking on the plan.

8. A.M. 2-06.4.9.H.d Review UDC Sections 7.4.9.B & .C and provide a Short-Term Bicycle parking detail that shows how these UDC sections are met.

9. A.M. 2-06.4.9.R Per TSM 7-01.4.1.A At least one (1) sidewalk is required to a project from each street on which the project has frontage. That said provide a sidewalk from the buildings to the street sidewalk along Speedway & Camilla Blvd.


If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

Sshield1 on DS1/planning/New Development Package/ DP13-0115

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package.
07/22/2013 LOREN MAKUS ENGINEERING REVIEW Approved
07/25/2013 RONALD BROWN H/C SITE REVIEW Denied SHEET 2
1. A sidewalk ramp leading to a marked area is shown at the N.E. corner of the building. What is this and why is it accessible?
2. Provide an accessible passenger loading zone in the shown passenger drop off area as required by the 2012 IBC, Section 1006.7 and the 2009 ICC A117.1, Section 503.
3. Modify note 18 to read "...Section 406 and 405 as applicable. Reference details J and G/4.
4. Outline the accessible parking design and reference it to detail J/4.
5. Show detectable warning strips at both ends of the marked crossing as per 2009 ICC A117.1, Sections 3406.12, 13 and 14 as applicable.
SHEET 4
6. Please label the Accessible Parking detail as detail "J".
a. Show a detectable warning strip at the north end of the marked crossing.
7. At detail G, show the detectable warning strip at the bottom of the ramp as required by section 406.12, 13 and/or 14 as applicable.
8. At detail E, add a note behind the "slope per plan" text to say "2% Maximum".
END OF REVIEW
08/01/2013 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change The following comments pertain to:

ADMINISTRATIVE MANUAL

SECTION 2-10.0.0: LANDSCAPE PLAN REQUIREMENTS

UNIFIED DEVELOPMENT CODE

1. Landscape requirements apply to the entire site.

2. The following information must be provided on Landscape plans:

3. Height of screening material and reference point for measurement

4. Location, size, and name of existing vegetation to remain in place for entire site

5. Landscape areas will be depressed to accept water flow from roofs, PAAL, and parking areas. Show by detail or spot elevations how landscape areas will accommodate water harvesting.

UNIFIED DEVELOPMENT CODE

7.6. LANDSCAPING AND SCREENING

1. Street landscape borders must be a minimum of ten feet wide as measured from the street property line. On streets designated as Major Streets and Routes (MS&R), the street landscape border must be measured from the future MS&R right-of-way line. Portions of street landscape buffer are not 10' wide.

2. Street landscape borders must be located entirely on site, except that, if approved by the City Engineer or designee, up to five feet of the required ten foot width may be placed within the adjacent right-of-way area or within the Major Streets and Routes (MS&R) right-of-way area on MS&R streets. Obtain permission for use ROW if necessary.

3. Within a vehicular use area, one canopy tree is required for each four motor vehicle parking spaces or fraction thereof. The canopy trees must be evenly distributed throughout the vehicular use area. Every parking space must be located within 40 feet of the trunk of a canopy tree (as measured from the center of the tree trunk). Provide required trees for parking lot.

4. The site, grading and landscape plans must show identical site layout to avoid conflict between the plans. Ensure that all changes to the other documents within the development package are reflected on the landscape plan.

5. If necessary include with re-submittal variance or administrative approval documentation. If necessary indicate on the lower right hand corner of all plans, the variance case number, date of approval, and any conditions imposed

6. Additional comments may apply
08/01/2013 ANDREW CONNOR NPPO REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/20/2013 CPIERCE1 OUT TO CUSTOMER Completed
12/20/2013 CPIERCE1 REJECT SHELF Completed