Permit Number: DP13-0096
Parcel: 99999999A

Address:
4146 N ORACLE RD

Review Status: Completed

Review Details: SITE and/or GRADING

Permit Number - DP13-0096
Review Name: SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/29/2013 STEVE SHIELDS ZONING REVIEW Denied It appears that the provided number of short-term bicycle parking spaces in incorrect. Based on UDC Section 7.4.9.B.2.d A single rack is designed and located to accommodate two bicycles. That said the provides should be 16.

The distance shown between racks on detail 2 does not meet the requirements of UDC Section 7.4.9.B.2.f and Figure 7.4.9-C.

Demonstrate on the plan or detail the requirements of UDC Sections 7.4.9.B.2.g & .h
05/29/2013 LOREN MAKUS ENGINEERING REVIEW Approved
05/30/2013 ANDREW CONNOR NPPO REVIEW Approv-Cond
05/30/2013 KEN BROUILLETTE FIRE REVIEW Approved
05/30/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/30/2013 ANDREW CONNOR LANDSCAPE REVIEW Approv-Cond LANDSCAPE APPROVAL SIGNATURE WHEN ZONING COMMENTS AND CONCERN ARE ADDRESSED
05/31/2013 RBROWN1 ADA REVIEW Passed
05/31/2013 RONALD BROWN H/C SITE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/07/2013 CPIERCE1 OUT TO CUSTOMER Completed