Permit Number: DP13-0071
Parcel: 14044009K

Address:
7632 S WILMOT RD

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP13-0071
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/14/2013 CPIERCE1 START PLANS SUBMITTED Completed
11/20/2013 STEVE SHIELDS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Planning and Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: Carl's Jr @ 7632 S. Wilmot
Development Package (3nd Review)
DP13-0071

TRANSMITTAL DATE: November 21, 2013

DEVELOPMENT PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Unified Development Code (UDC), Administrative Manual (AM) & Technical Standards Manual (TSM) were addressed.

1. Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is May 15, 2014.

2. This proposed development was reviewed for full code compliance with the Unified Development Code (UDC), Administrative Manual (AM) & Technical Standards Manual (TSM).

The following comments are based on the requirements of Administrative Manual (AM) 2-06.3.0 FORMAT REQUIREMENTS.

3. This comment was not addressed. Zoning was not able to find the bearing and distance for "L1". A.M. 2-06.4.8.A Provide site boundary information, including bearing in degrees, minutes, and seconds, with basis for bearing noted. That said there is an "L1" listed at the north end of a future access isle, provide the boundary information for "L1".

4. This comment was not fully addressed. Provide the zoning for the parcels to the east of Wilmot Road. A.M. 2-06.4.9.F All existing zoning classifications on and adjacent to the project (including across any adjacent right-of-way) shall be indicated on the drawing with zoning boundaries clearly defined.

5. A.M. 2-06.4.9.H.5.d The bicycle parking spaces calculation is not correct. Based on detail C7.0.4 the provided number of short term bicycle parking spaces should be listed as 4. See UDC Section 7.4.9.B.2.d.

6. A.M. 2-06.4.9.H.5.d Detail C4.1.4 does not meet the requirements of UDC 7.4.9.B.2.f, & .g. UDC Section 7.4.9.B.2.f Show the 2' x 6' space on the detail. UDC Section 7.4.9.B.2.g Show a 2'-6' dimension from the rack to the proposed bicycle locker. See UDC Figure 7.4.9-C

7. This comment was not addressed. A.M. 2-06.4.9.Q Provide the proposed height of the building within the footprint on the site plan.

8. Provide a copy of the required cross access and parking agreement with your next submittal, see rezoning comment 8.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.com

Sshield1 on DS1/planning/New Development Package/ DP13-0077

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package & copy required cross access and parking agreement.
11/21/2013 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved Regional Traffic Engineering has no comments on the development and supports its acceptance. Thank you.
11/21/2013 MARTIN BROWN COT NON-DSD FIRE Denied REFER TO REDLINES ON SHEET 10.0
12/02/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show the location and rim elevations of the proposed public manholes that the overall developer is to be installing. [Initial comment: Revise the site drawing to include the following information:
a. The invert and rim elevations of all manholes and cleanouts; along with the Pima County Wastewater Management Department (PCWMD) reference number.
b. Any existing or proposed utility easements
Reference: City of Tucson Administrative Manual No. 2-06.0.0, Section 4.8 and Section 107.2.13, IBC 2012.]
2. Clarify the location of the proposed extension of the public sewer; the connection of the proposed sewer does not appear to connect to the existing public sewer located on South Wilmot Road. [Initial comment: Verify the proposed point of connection to the public sewer; the records for Pima County Wastewater Management do not show any sanitary sewers or manholes located west of Wilmot Road at that location.]
12/11/2013 RONALD BROWN ZONING HC REVIEW Reqs Change SHEET C3.0
1. As per ICC A117.1, Section 406.12, the detectable warning strip is to be only 24" deep. Revise all detectable warning strips to this size and resubmit.
2. The detectable warning strip at the north end of the marked crossing traversing the most northerly drive entrance needs to be relocated to the face of the marked crossing and in the direction of travel as required by Section 406.13.1.
3. Delete the detectable warning strip at the accessible parking aisle. This is a safe zone.
4. Delete the curb ramp and detectable warning strip going to the dumpster. This is not an accessible route.
5. Show the dimension of the most northerly marked crossing.
SHEET C7.0
6. At detail C7.0.12 reference review comment 1 above.
7. Revise all lettering for all sheets to City of Tucson standard of 3/32" minimum actual size both upper and lower case and resubmit.
8. At detail C7.0.3, delete note 1 of the Van Accessible sign detail.
9. At detail C7.0.13 delete the detectable warning strip, the accessible aisle is a safe zone.
END OF REVIEW
12/12/2013 ZELIN CANCHOLA COT NON-DSD TRAFFIC Denied CDRC TRANSMITTAL

TO: Planning and Development Services Department
Plans Coordination Office

FROM: Zelin Canchola
TDOT

PROJECT: Carl's Jr @ 7632 S. Wilmot
Development Package (2nd Review)
DP13-0071

TRANSMITTAL DATE: December 12, 2013

Develpoment plan denied. Previous comments were not addressed.

Development plan must reflect offsite improvements into the development site.

Refer to rezoning condition #26:

Owner/developer shall design and buildout the west half of the Major Streets and Routes improvements to wilmot road (along the Wilmot frontage of the site) including appropriate pavement transistions beyond the limits of the improved section, 6 foot wide sidewalks and curbing along the west side of wilmot road, turn lanes and extension of the 48 in CMP with RCP to the west Right of Way line.

The response that bike lanes are not required is not acceptable. Although no recommendations are identified within the traffic study, bike lanes are always incorporated with full build out requirements, especially with new turn lanes and striping.

1. Marked southbound turn lane, with bike lane included, shall be incorperated into
site plan with a minimum storage of 100 feet.

Turn radius shall be indicated according to development standard (Technical Standards
Manual Section 10-01 Minimum curb return radius, on development plan.

Site visibility triangles shall be shown on development plan according to Technical
Standards Manual Section 10.01.5.0 for entrance to project site from wilmot as well
as the driveways from local access.

Include note: A private improvement agreement (PIA) with the city of tucson will be required for work within the right of way call 791-4259 for further information.

Change any reference to Town of Tucson to City of Tucson.
12/13/2013 ELIZABETH LEIBOLD ENGINEERING REVIEW Denied DATE: December 13, 2013
TO: Mark Johnson, P.E., Bury + Partners-Holdings, Inc
SUBJECT: Development Package Engineering Review resubmittal
PROJECT: Carl's Jr Restaurant Development Package
LOCATION: 7632 S WILMOT RD, Ward 5
FEMA PANEL: 2905 L, X-unshaded
REVIEWER: Elizabeth Leibold
ACTIVITY NUMBER: DP13-0071

SUMMARY: The resubmittal for the Development Package including site plan, grading plans, copy of Drainage Report, Geotechnical Engineering Report and TIA on diskette, drainage report, response letter and other documents was submitted and reviewed. Due to significant number of remaining comments, additional review comments may be forthcoming. Development Services Department Engineering Division does not recommend approval of the Development Plan at this time until the following comments are addressed. A meeting is required prior to resubmittal due to substantial number of comments that do not appear to be addressed.

BASE PLAN SHEETS COMMENTS:
1) City of Tucson Administrative Manual Section (Admin Man Sec.) 2-06.4: Assure sheets are numbered sequentially for all sheets (including landscaping sheets) in Development Package. Add approval box to each sheet: http://cms3.tucsonaz.gov/pdsd/cdrc-rezoning/cdrd-stamp
2) Admin Man Sec.2-06.4.8.B: On sheets C1.0, C4.0, and C6.0 at minimum, show all easements on and immediately adjacent to or overlapping the Carl's Jr parcel per Final Plat sheets 2, 3, & 4.
MASTER COVER SHEETS/ GENERAL NOTES:
3) Admin Man sec.2-06.4.7.B: List the remaining notes on plan under drainage or general notes:
a) "The developer, any successors and assigns, will hold the City of Tucson, its officers, employees, and agents harmless from any and all claims for damages related to the use of this development as shown hereon, now and in the future, by reason of flooding, flowage, erosion, or damage caused by water, whether surface flood or rainfall."
b) "Drainage will remain in its natural state and will not be altered, disturbed, or obstructed other than as shown on this site plan."
c) Add a note stating that the project is designed to meet the overlay zone criteria: LUC Sec. 2.8.3, Major Streets and Routes (MS&R) Setback Zone.
d) Tech Man Sec.4-02.14.3: Add note to clarify: Maintenance of onsite drainage facilities is the responsibility of the owner.
4) Admin Man Sec.2-06.4.4: Clarify for the project-location map on cover sheet. The project-location map, shall cover approximately one square mile, be drawn at a minimum scale of three inch equals one mile.
DRAINAGE COMMENTS:
5) Admin Man Sec.2-06.4.8.H: Significant number of comments were not addressed - see comments:
a) Show existing stormdrain system (pipe sises) running along Wilmot frontage and spine road adjacent to Carl's Jr project.
b) On site and grading sheets, label elevations for clean-outs / junction manhole rims and inverts along existing storm sewer system.
c) Provide drainage report aside from master report that explains design for Carl's Jr that is not shown in master report, specifically addressing the following comments:
i) The proposed basin shall show positive gradients and bleed off to storm drain system if other bleed off is not provided.
ii) Clarify on plans or explain how end of stormdrain pipes function.
iii) Address proposed system in addendum/report, that provides direction of flow on drainage report exhibit(s).
iv) Show positive gradients with any necessary bleed-off pipes, so that no potential ponding occurs.
v) If retention systems are intended, address the following:
(1) explain how the amount of runoff from developed conditions exceed 9 cfs (which is accounted for in master drainage plan).
(2) Provide factor of safety for percolation.
(3) Provide infiltration testing results for proposed location of retention system.
vi) Provide a discussion and exhibit for offsite watersheds.
vii) Show existing stormwater drainage pipe at south side of project on drainage exhibits.
viii) Include discussion of stormwater that comes from offsite drainage from the east to the site and is conveyed by stormdrain system recently constructed.
ix) Discuss in Drainage Report and label on Development Package planviews on site sheet water harvesting areas.
x) Label locations of Q100 entering and exiting the site on drainage exhibits, and on grading plan sheet.
xi) Provide administrative address and activity number (DP13-0071) on the report cover page.
xii) Provide verification that any drainage solutions which occur outside the boundaries of the parcel are constructed with adjacent owners' permission. (If not accounted for on Final Plat, additional notarized documentation of that approval will be submitted with the drainage report.)
d) Delineate and label geotechnical recommended horizontal setbacks from basin to proposed building and pavement structures on planviews.
SITE COMMENTS:
6) Not all the information was provided. The following information regarding existing private or public right-of-way adjacent to or within the site shall be provided: the name, right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts, and sidewalks. Show existing or proposed sidewalks along abutting right-of-way for Wilmot Road. Label the MS&R future sidewalk (6-ft min width) along Wilmot.
7) Some of the existing utilities are shown yet not clearly labeled. The following information regarding existing utilities shall be provided: the location of any existing fire hydrants, sanitary and storm sewers, including the pipe diameter and the invert and rim elevations of all manholes and cleanouts; the Pima County Wastewater Management Department (PCWMD) reference number; locations of gas lines, electric and telephone lines, poles, and communications cables, on-ground junction boxes, and street lights. Assure that the existing sanitary sewer line is shown on grading sheet and sections provided where proposed infrastructure is in close proximity to existing utilities. Show sufficient setback distances and cover between existing and proposed underground pipes / utilities.
8) Remove / shift trees from sight visibility triangles on sheet L1.0
9) Show sight visibility triangles for Wilmot Road on sheet C4.0.
SURVEY RELATED COMMENTS:
10) Title report not found in paperwork. Assure that all easements listed on the Schedule B of title report are clearly drawn, labeled with Book/page or Docket/page, and/or listed as a blanket easement, and/or labeled with accurate dimensions and bearings on the plat. Provide a copy of the Title Report, Schedule B with current easement data.

Address also redlines on plans and provide copy of redlines with resubmittal. A response letter is required with the resubmittal of the revised Development Plan package, acknowledging or addressing all of the above comments. For resubmittal, provide response letter, title report, revised plan sheets, drainage report specific to site, copy of geotechnical report, copy of TIA, Final Drainage Report (master report), diskette, and sheet location where comment is addressed. Meeting is required prior to resubmittal. If you have questions, call me at 837-4934.

Elizabeth Leibold, P.E., CPM, CFM
Civil Engineer
Engineering Division
Planning & Development Services Dept
12/13/2013 JOE LINVILLE LANDSCAPE REVIEW Reqs Change 1) Revise the Native Plant Preservation Plan to restore the aerial photo.

2) Revise the tree calculations on L1.0 to comply with UDC 7.6.4.B.1.a and & 7.6.4.C.1.a. The calculation for parking lot trees is incorrect and based on the previous code. There is also a 50% landscape coverage calculation required for the Wilmot Rd border. The calculation is exclusive of any plants provided to meet the screening requirements.

3) Revise note on the Native Plant Preservation Plan to cite City Codes. Note 7 under Standard Specifications references a County Code.
12/16/2013 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Reqs Change This review has been completed and resubmittal is required. Please resubmit the following items:

1) 2 rolled sets of the plans.
2) All items requested by review staff
3) All items needed to approve this plan.
4) A disk containing all items submitted.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/17/2014 CPIERCE1 REJECT SHELF Completed