Permit Number: DP13-0054
Parcel: 11304348A

Review Status: Completed

Review Details: SITE and/or GRADING

Permit Number - DP13-0054
Review Name: SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/29/2013 STEVE SHIELDS ZONING REVIEW Approved CDRC TRANSMITTAL

TO: Planning and Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: Ice Kiosk @ 1235 E. Fort Lowell Road
Development Package (1st Review)
DP13-0054


TRANSMITTAL DATE: March 29, 2013

DEVELOPMENT PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Unified Development Code (UDC), Administrative Manual (AM) & Technical Standards Manual (TSM) were addressed.

The following comments are based on Unified Development Code (UDC) Administrative Manual (AM) 2-06.0:

1. A.M. 2-06.4.9.O Show the future curb along Fort Lowell Road and provide a perimeter yard setback dimension from the proposed structure to the back of future curb. Future curb is located 11' from the existing property line.

2. As a architects stamp is shown on the plan the architects signature and date is required.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

Sshield1 on DS1/planning/New Development Package/ DP13-0054

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package & recorded MS&R covenant
05/13/2013 RBROWN1 ADA REVIEW Passed
05/13/2013 JASON GREEN ENGINEERING REVIEW Approved May 13, 2013
FLOODPLAIN USE PERMIT NO.: T13OT00579
ADDRESS: 1235 E Ft Lowell Rd Tucson, Arizona 85719
PROPERTY OWNER: All B's Car Wash LLC
4951 E Grant Rd STE 105 PMB 252 Tucson, Arizona 85712

The applicant is authorized to use a portion of the FEMA Special Flood Hazard Area Zone AE per the Flood Insurance Rate Maps 04019C1689L, specifically described as:

A portion of Parcel 113-04-348A

For the purpose of installing an Ice and Water Kiosk within the vehicular use area.

The applicant agrees to comply with City of Tucson Floodplain and Erosion Hazard Area Regulations. Violation of any of the conditions stated or referred to below, as determined by the City Engineer, shall be grounds for revocation of this permit. Issuance of this permit does not constitute a waiver of other requirements contained in the Tucson City Code, Unified Development Code, or any other Federal, State, or local regulation. No use other than as permitted herein is allowed. Additional uses allowed under City of Tucson Floodplain and Erosion Hazard Regulations require application for review and approval of an additional Floodplain Use Permit.

The following 11 conditions apply to this permit:

1) This permit becomes invalid and is subject to additional floodplain review, if any required development changes the construction of the Kiosk, or, if there is any further disturbance within the floodplain other than that outlined in this application. This floodplain use permit may be subject to conditions or restrictions designed to reduce or mitigate the potential damage or hazard to life or property resulting from the construction of the generator within the regulatory floodplain, floodway or erosion hazard areas as determined by the project engineer and accepted by the City of Tucson.

2) Except as approved by the City Engineer prior to the start of construction, development under this permit shall not obstruct, retard or divert the existing flow of floodwaters from or to adjacent properties.

3) For purposes of this permit the following flood elevations shall be used for the enclosed detached garage:
Base Flood Elevation (BFE) = 2370.4 feet NAVD 1988
Regulatory Flood Elevation (RFE) = 2371.4 feet NAVD 1988
Electrical Equipment within the Kiosk is to be elevated at or above the Regulatory Flood Elevation (RFE). Connections that are below the BFE must be designed to with stand 60 minutes of submergence in floodwaters.

4) Floodplain Approval of elevation certificate, prepared by an Arizona State Registered Land Surveyor, is required prior to the finished construction or Final Inspection (P2F). The Elevation Certificate must include the identity and elevation of the lowest service equipment/machinery servicing the Kiosk.

5) All work shall conform to the approved development plan documents, which are made part of this permit. The Kiosk is to be firmly anchored to prevent flotation per TUC Code Sec.26-5.2.10.

6) Within 5 (five) days of issuance of this permit, and through completion of the project, notification must be posted and maintained in a conspicuous place on the job site stating "CONSTRUCTION PROCEEDING UNDER REQUIREMENTS OF CITY OF TUCSON FLOODPLAIN USE PERMIT # T13OT00479 FOR INFORMATION PLEASE CALL 791-5550."

7) This Floodplain Use Permit and plans shall be kept in a readily accessible location on site at all times.

8) Any additional future disturbance of the floodplain shall have separate floodplain use permit applications submitted to this office for review and approval.

9) See the associated activity DP13-0054 and T13CM01363

10) This permit is specific to the improvements for 1235 E Fort Lowell Rd as indicated on the approved plans. It shall not apply to any other structure or property, whether attached or unattached, not specified under this permit.

11) Renewal of this permit will require a new application, review and approval of that application by the City of Tucson, Planning & Development Services Department, Engineering Division. This permit may be renewed for up to one year, in the absence of Registered Plant authorization, at the sole discretion of the City Engineer or designated representatives.

This Floodplain Use Permit will be automatically revoked and becomes invalid if conditions are not complied with, as set forth in this permit.

APPLICANT NAME: Bessie Guadiana-Hoffman
ADDRESS: 1551 S 2nd Ave Tucson, AZ 85713
PHONE: 520-241-0880
OWNER: All B's Car Wash LLC
ADDRESS: 4951E Grant Rd Tucson, Arizona 85712
PHONE: 520-954-7777

(EXPIRATION DATE) Month: _05 Day: 13 Year: 2014

SIGNATURE OF APPLICANT DATE

The applicant is authorized by the City Engineer to receive a floodplain use permit subject to the above referenced conditions and restrictions.
05/13/2013 RONALD BROWN H/C SITE REVIEW Approved
05/14/2013 KEN BROUILLETTE FIRE REVIEW Approved
05/14/2013 ANDREW CONNOR NPPO REVIEW Approved
05/14/2013 ANDREW CONNOR LANDSCAPE REVIEW Approved
05/30/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/03/2013 CPIERCE1 OUT TO CUSTOMER Completed