Permit Number: DP13-0042
Parcel: 13313006N

Review Status: Completed

Review Details: SITE and/or GRADING

Permit Number - DP13-0042
Review Name: SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/13/2013 KEN BROUILLETTE FIRE REVIEW Approved
03/13/2013 RBROWN1 ADA REVIEW Passed
03/13/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
03/13/2013 RONALD BROWN H/C SITE REVIEW Denied 1. As per the 2012 IBC, Table 1106.1, 7 accessible parking spaces are required for 221 total parking spaces.
a. Of that 7 accessible parking spaces, 2 must be Van Accessible. Please show on site plan.
2. At the most Easterly parking space:
a. Space is not accessible. The extended curb has cut the 18' length required to something less than 18'. It has also shorten the accessible aisle.
b. Section 3/A5.0 which cuts down the middle of the access aisle shows a 6" curb with no ramp for access to the accessible route and store entrances.
3. For all new accessible parking spaces, confirm grade slopes of 2% maximum in all directions and indicate such on plan.
4. Detail 8/A0.3: The 5'-0" height is not correct. Please provide 7'-0" a.f.g. to the bottom of then sign as per COT DOT sign standards.
a. Also include a "Van Accessible" sign.
5. At detail 3/A0.2:
a. On sheet A0.1 the existing north west accessible parking space is eliminated. On this detail it remains. Please reconcile.
b. The accessible parking symbol is missing from the accessible parking space located in the middle.
6. At detail 4/A0.2, the far east accessibkle parking space is non-compliant. The curb extension into this space has made it and the accessible parking ailse too short.
a. The section through the aisle shows a 6" high curb. There is no ramp shown for access from the aisle.
7. At detail 6/A0.3
a. Generic details are not acceptable. Provide actual accessible parking space layout with all dimensions including van accessible, signage, slopes, markings and access (ramps as required) to the accessible route for all different types of accessible parking layouts.
END OF REVIEW
03/14/2013 LOREN MAKUS ENGINEERING REVIEW Approved
03/14/2013 STEVE SHIELDS ZONING REVIEW Approved
03/15/2013 ANDREW CONNOR NPPO REVIEW Approved
03/15/2013 ANDREW CONNOR LANDSCAPE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/04/2013 CPIERCE1 OUT TO CUSTOMER Completed