Permit Number: DP13-0030
Parcel: 116126300

Review Status: Completed

Review Details: SITE and/or GRADING

Permit Number - DP13-0030
Review Name: SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2013 STEVE SHIELDS ZONING REVIEW Approved
02/25/2013 RONALD BROWN H/C SITE REVIEW Denied 1. Indicate maximum slope of 2% in all directions at all areas of the accessible parking.
2. Provide detectable warnings at both ends of the marked crossing.
3. At detail 5, separate the "Van Accessible" sign from the main accessible parkings sign.
a. Indicate a mounting height of 7'-0" to the bottom of the main accessible parking sign.
END OF REVIEW
02/25/2013 LOREN MAKUS ENGINEERING REVIEW Approved
02/27/2013 ANDREW CONNOR NPPO REVIEW Approved
02/27/2013 MARTIN BROWN FIRE REVIEW Approved
02/27/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/27/2013 ANDREW CONNOR LANDSCAPE REVIEW Approved
02/27/2013 RBROWN1 ADA REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
02/27/2013 SHANAE POWELL OUT TO CUSTOMER Completed