Permit Number: DP13-0018
Parcel: 12310036E

Review Status: Completed

Review Details: RESUB - SITE and/or GRADING

Permit Number - DP13-0018
Review Name: RESUB - SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/30/2013 KEN BROUILLETTE FIRE REVIEW Approved
06/05/2013 JASON GREEN ENGINEERING REVIEW Denied DATE: June 11, 2013
SUBJECT: McDonald's on Speedway Development Plan Package- 2nd Engineering Review
TO: Kelly Ferguson
LOCATION: 1711 E Speedway Blvd; T14S R14E Sec06
REVIEWERS: Jason Green, CFM
ACTIVITY: DP13-0018

SUMMARY: Engineering Division of Planning & Development Services Department has received and reviewed the proposed Development Plan Package and Drainage Statement (Wood/Patel; 20MAY13). Engineering Division does not recommend approval of the Development Plan Package at this time. This review falls under the Unified Development Code (UDC), Administration Manual (AM) and Technical Standards Manual (TSM). Refer to the links for further clarification:
http://cms3.tucsonaz.gov/files/planning/UDC_ADOPTED_100912.pdf; http://cms3.tucsonaz.gov/files/planning/Technical_Manual_ADOPTED_100912.pdf; http://cms3.tucsonaz.gov/files/planning/Admin_Manual_ADOPTED_100912.pdf

The following items need to be addressed:

SITE PLAN:

1) AM Sec.2-06.4.9.H.1: Revise the development plan document to label the required 25-foot radii at both driveway locations on the MS&R Street; Speedway Blvd, per City of Tucson Transportation Access Management Guidelines (TAMG), Section 5.5. Refer to TSM Sec.10-01 for street development standards. Provide written approval from TDOT if smaller curb returns are being proposed.

2) AM Sec.2-06.4.9.H.2: Revise the development plan document to dimension the existing/future SVTs for both driveway entrances. Either provide the dimensions in plan view or label them in Keynote #21.


GENERAL COMMENTS:

Please provide a revised Development Plan Package that addresses the comment provided above. For expedite purposes the development plan package can be reviewed over the counter (PDSD Engineering Division comment only) for stamp approval once all items have been addressed. Please call to schedule an appointment when ready.

For any questions or to schedule meetings call me at 837-4929.


Jason Green, CFM
Senior Engineer Associate
Engineering Division
Planning & Development Services Department
06/10/2013 STEVE SHIELDS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Planning and Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: McDonald's @ 1711 E. Speedway Blvd.
Development Package (2nd Review)
DP13-0018

TRANSMITTAL DATE: June 10, 2013

DEVELOPMENT PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Unified Development Code (UDC), Administrative Manual (AM) & Technical Standards Manual (TSM) were addressed.

1. This site was reviewed for full code compliance for the entire site.

2. Remove all references to the Land Use Code (LUC) from the plans and replace with Unified Development Code (UDC) references. Sheet 4 still has references to the LUC see General Note 3. There are also references to Development Standards that do not apply, see General Note 6 & 17.

The following comments are based on Unified Development Code (UDC) Administrative Manual (AM) 2-06.0:

1. A.M. 2-06.4.4 The location map shown on the cover sheet is difficult to read. Either remove the parcels from the map or lighten the plan show that the section corners can be read.

2. General Note 3, Sheet 4 still references the LUC. A.M. 2-06.4.7.A.4 Identify the existing and proposed use of the property as classified per the UDC. List all UDC sections applicable to the proposed uses. General Note 3 references the LUC.

The following comments are based on Sheet 14, SITE PLAN:

1. A.M. 2-06.4.9.H.5.a Per UDC Section 7.4.4.B and Table 7.4.4-1 the required number of vehicle parking spaces is 4,197 s.f./100 = 45 and number provided is 20. A Board of Adjustment for Variance (B of A) is required to reduce the parking required. If approved provide the B of A case number, what was approved, and any conditions of approval on the plan.

2. A.M. 2-06.4.9.H.5.d Detail 3/SD3 remove the reference to "28" MIN. CLEARANCE BETWEEN MULITIPLE DOUBLE RACK INSTALLATIONS" from the detail as this is not correct.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

Sshield1 on DS1/planning/New Development Package/ DP13-0018

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package.
06/13/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/18/2013 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change 1. A 30" continuous screen along street frontages for vehicle use area must be provided per DS 7.6.4-I. Portion of the street landscape border to the east of the ingress/ egress appears to have insufficient screening.

2. Indicate the location and height of all screening elements.

3. Note: The screening requirement is in addition to the landscape requirements.

4. If necessary: Include with re-submittal variance approval documentation. Indicate on the lower right hand corner of the site plan, the variance case number, date of approval, and any conditions imposed.

5. The site plan and landscape plan must show identical site layout to avoid conflict between the two plans. Ensure that all changes are reflected on the landscape plan.

6. Additional comments may apply

Final Status

Task End Date Reviewer's Name Type of Review Description
11/27/2013 CPIERCE1 REJECT SHELF Completed