Review Date Reviewer's Name Type of Review Description Status Comments
01/28/2013 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
01/29/2013 TIM ROWE PIMA COUNTY WASTEWATER Passed Per RWRD form
01/30/2013 RONALD BROWN ADA REVIEW Passed
01/31/2013 STEVE SHIELDS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Planning and Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: Saint Augustine Catholic High School Proposed Expansion
Development Package (1st Review)
DP13-0016

TRANSMITTAL DATE: February 8, 2013

DEVELOPMENT PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Unified Development Code (UDC), Administrative Manual (AM) & Technical Standards Manual (TSM) were addressed.

1. Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is January 27, 2014.

2. This site was reviewed for full code compliance for the entire site due to a cumulative expansion of building gross floor area (GFA) greater than 25%. See T09CM00578.

The following comments are based on Unified Development Code (UDC) Administrative Manual (AM) 2-06.0:

1. A.M. 2-06.4.9.E There appears to be some type of lot split/reconfiguration proposed for the northwest area of this site, between parcels 136-01-001B & 136-06-002C. Based on Pima County Assessor's Record Map the existing property line runs along the existing section line and you are proposing to move the property line west. A lot line reconfiguration will need to be processed through the PDSD prior to approval of the development package.

2. A.M. 2-06.4.9.G It appears that phasing of the project is proposed but only one phase is shown. Show all additional phases on the plan. If the project is to be phased, provide calculations, setbacks, etc., to indicate that each phase complies with all requirements as a separate entity. Show phase lines on the drawing.

3. A.M. 2-06.4.9.H.2 Show future and existing sight visibility triangles (SVT's). On a designated MS&R street, the sight visibility triangles are based on the MS&R cross-section.

4. A.M. 2-06.4.9.H.2 There are future SVT's shown on sheet 6 that are not shown correctly review, see TSM 10-01.5.0.

5. A.M. 2-06.4.9.H.5 Provide a width dimension for the existing access lane shown along the east property line. As this is full code compliance demonstrate on the plan how the requirements of UDC Section 7.4.6.H.1 are met for this access lane.

6. A.M. 2-06.4.9.H.5 Sheet 8 demonstrate on the plan how the requirement of UDC Section 7.4.6.H.1 are met for the entire length of the propose access lane.

7. A.M. 2-06.4.9.H.5.a Sheet 2 detail 1 the parking bumper dimension is not correct. Per UDC Section 7.4.6.H.3 this dimension is 2'-6".

8. A.M. 2-06.4.9.H.5.a Sheet 2 detail 1 provide a Parking Angle and Space Depth dimension for the proposed angled parking.

9. A.M. 2-06.4.9.H.5.a Sheet 2 detail 2 the over hang is not shown correctly. Per UDC Section 7.4.6.H.3 this overhang is 2'-6" and the remaining parking space should be 15'-6" not 15'.

10. A.M. 2-06.4.9.H.5.a Provide a Passenger Drop-Off Area calculation on the plan, see UDC Section 4.9.3.E.7, and show the drop-off areas on the plan.

11. A.M. 2-06.4.9.H.5.c The loading space calculation is not correct. Per UDC Section 7.5.5, Civic Use Group, Education Use, 0 required.

12. A.M. 2-06.4.9.H.5.d As this is full code provide a detail for both the Short & Long term bicycle parking and clearing indicated on the plan the locations for both Short & Long term bicycle parking.

13. A.M. 2-06.4.9.L If applicable all proposed easements (utility, sewer, drainage, access, etc.) are to be dimensioned and labeled as to their purposes and whether they will be public or private. The easements may have to be recorded and the recordation information added to the development package prior to approval.

14. A.M. 2-06.4.9.R As this is full code demonstrate on the plan how the requirements of TSM 7-01.3.3 are met.

15. A.M. 2-06.4.9.R Provide width dimension for all proposed and existing sidewalks on site.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

Sshield1 on DS1/planning/New Development Package/ DP13-0016

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package.
01/31/2013 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved The development's location lies outside of any ADOT facilities and its acceptance is recommended. Thank you.

________________________________

Confidentiality and Nondisclosure Notice: This email transmission and any attachments are intended for use by the person(s)/entity(ies) named above and may contain confidential/privileged information. Any unauthorized use, disclosure or distribution is strictly prohibited. If you are not the intended recipient, please contact the sender by email, and delete or destroy all copies plus attachments.
.
02/04/2013 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved 4350 E. Irvington Road
Post Office Box 711, Tucson, AZ 85702


WR#259127 February 4, 2013


Baker & Associates Engineering
3561 E. Sunrise Dr.
Tucson, Arizona 85718

Dear Baker Engineering:

SUBJECT: St. Augustine Catholic High School
DP13-0016

Tucson Electric Power Company (TEP) has reviewed and approved the development plan submitted January 31, 2013. There are no existing facilities within the boundaries of this proposed development.

In order to apply for electric service, call the New Construction Department at (520) 918-8300. Submit a final set of plans including approved site, electrical load, paving off-site improvements and irrigation plans, if available include a CD with the AutoCAD version of the plans.

If easements are required, they will be secured by separate instrument. Your final plans should be sent to:
Tucson Electric Power Company
Attn: Mr. Richard Harrington
New Business Project Manager
P. O. Box 711 (OH-204)
Tucson, AZ 85702
520-917-8726

Should you have any technical questions, please call the area Designer Charles Leon at (520) 917-8707.

Sincerely,


Joann Hayes
Administrative 1
Design/Build
jh
Enclosures
cc: DSD_CDRC@tucsonaz.gov, City of Tucson (email)
C. Leon, Tucson Electric Power
M. Burke, Tucson Electric Power
02/05/2013 PGEHLEN1 UTILITIES SOUTHWEST GAS Approved See Letter in SIRE
02/08/2013 PGEHLEN1 COT NON-DSD ENVIRONMENTAL SERVICES Denied This project is not approved by Environmental Services. I cannot find notes on cover sheet for waste management or recycle or anything on the plan view drawings.




Jeff Drumm, P.E.
Environmental Manager
City of Tucson Environmental Services
520-837-3713
02/11/2013 PGEHLEN1 OTHER AGENCIES PIMA ASSN OF GOVTS Approved Here are my comments -

DATE: 2/11/2013
CASE: DP13-0016 ST AUGUSTINE CATHOLIC HIGH SCHOOL
COMMENT: No objections or adverse comments

Daily PM Peak
Vehicle Trip Generation: 5,655 282

Thanks,
-Eric

Additional notes: Detailed traffic impact analysis has been conducted

See SIRE for additional documents
02/13/2013 PGEHLEN1 COT NON-DSD TUCSON POLICE DEPARTMENT Approved I have no issues with this request.

CSO Becky Noel #37968
Tucson Police Dept
837-7428
02/19/2013 JOHN BEALL COT NON-DSD COMMUNITY PLANNING Passed
02/21/2013 RONALD BROWN ZONING HC REVIEW Denied SHEET 2
1. For all accessible routes crossing an auto entrance, provide a complete marked crossing with ramps, markings, and detectable warnings required by ICC A117.1, Sections 406.1 and 406.12, 13 and 14.
a. Provide a large scale detail of all the different types of ramps including marking, slopes, dimensions, and detectable warnings as required.
2. At detail 2:
a. Delete the generic accessible parking details and provide details of the actual accessible parking layout/s showing all accessible requirements as dimensions, slopes, markings, signage, access to accessible route, ramps as required, and aisles.
b. Insure 1 of every six accessible spaces is a "Van Accessible" space. Please such identify on the site plan.
SHEET 3
3. Ditto, review comment 1.
4. Provide a marked crossing at the drive entrance between the two groups of accessible parking.
5. Please provide an accessible passenger loading zone as required by the 2012 IBC, Section 1106.7 and ICC A117.1, Section 503.3.
6. Please provide an accessible route to all new athletic facilities and buildings as per the 2012 IBC, Chapter 11 and the 2009 Edition ICC A117.1.
7. Please provide accessible seating for both bleachers as per the 2012 IBC, Section 1108.2 and ICC A 117.1, Section 802.
SHEET 4
8. Ditto Review Comments 6 and 7 for all new sports facilities, building and seating.
END OF REVIEW
02/25/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the site drawing to include the following information:
a. The location and size of sanitary and storm sewers, including the pipe diameter and the invert and rim elevations of all manholes and cleanouts; along with the Pima County Wastewater Management Department (PCWMD) reference number.
b. Any existing or proposed utility easements
c. The first floor elevation for the proposed buildings
d. If an on-site sewage disposal system is located on site, show the location of all individual components for the disposal system, including any reserve areas and indicate the required separation distances.
Reference: City of Tucson Administrative Manual No. 2-06.0.0, Section 4.8 and Section 107.2.13, IBC 2012.
02/25/2013 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approved From Zelin Canchola TDOT Traffic Engineering
Date: February 26, 2013

RE: DP13-0016 St Augustine Development Package

New Public Roadways will be required to be built through the DOT Private Improvements Agreement Process. Continue to work with TDOT Traffic Engineering and Permits and Codes for traffic signal, and roadway improvements.
02/26/2013 JOE LINVILLE LANDSCAPE REVIEW Denied If the project is to be phased, provide calculations, grading limits, and landscape and screening improvements, etc., to indicate that each phase complies with all requirements as a separate entity. A.M. 2-06.4.9.G

Ensure that the landscape/NPP drawings coordinate with the site plan improvements. The review cannot commence until the scope of the project is established.
02/26/2013 PGEHLEN1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Approved January 31, 2013

Baker & Associates Engineering, Inc.
3561 E. Sunrise Dr., # 225
Tucson, AZ 85718

Attn: William H Baker Jr., P.E.

SUBJECT: Water Availability for project: St. Augustine Catholic High School, APN: 13606002C, Case #: N/A, T-14, R-15, SEC-22, Lots: 9999, Location Code: TUC, Total Area: 37ac Zoning: Rx-1

WATER SUPPLY
Tucson Water will provide water service to this project based on the subject zoning of the above parcels. Tucson Water has an assured water supply (AWS) designation from the State of Arizona Department of Water Resources (ADWR). An AWS designation means Tucson Water has met the criteria established by ADWR for demonstration of a 100-year water supply - it does not mean that water service is currently available to the subject project.

WATER SERVICE
The approval of water meter applications is subject to the current availability of water service at the time an application is received. The developer shall be required to submit a water master plan identifying, but not limited to: 1) Water Use; 2) Fire Flow Requirements; 3) Offsite/Onsite Water Facilities; 4) Loops and Proposed Connection Points to Existing Water System; and 5) Easements/Common Areas.

Any specific area plan fees, protected main/facility fees and/or other needed facilities' cost, are to be paid by the developer. If the existing water system is not capable of meeting the requirements of the proposed development, the developer shall be financially responsible for modifying or enhancing the existing water system to meet those needs.

This letter shall be null and void two years from the date of issuance.

Issuance of this letter is not to be construed as agency approval of a water plan or as containing construction review comments relative to conflicts with existing water lines and the proposed development.

If you have any questions, please call New Development at 791-4718.

Sincerely,


Scott Schladweiler, P.E.
Engineering Manager
Tucson Water Department

SS:bjp
CC:File
02/27/2013 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Reqs Change This review has been completed and revisions are required. Two rolled sets of the plan, a disk with all plans and documents included in the submittal package and all other items requested by review staff must be included with the next submittal of these plans.
02/27/2013 PGEHLEN1 OTHER AGENCIES TUCSON AIRPORT AUTHORITY Passed
02/27/2013 LOREN MAKUS ENGINEERING REVIEW Denied A previous drainage report was prepared for St. Augustine High School. Discuss the previous report and explain any differences in conclusions.

Show areas of existing pavement to be removed and show where existing driveways will be removed.

Clarify how the phasing is proposed. The improvements proposed for phase 1 don't seem to be coincident with the improvements for the future phases. The improvements shown on NPPP-1 can be approved, but future improvements will be subject to full review. Present a plan that clearly shows just these improvemenst.
02/27/2013 JENNIFER STEPHENS PIMA COUNTY ADDRESSING Approved AUDREY FARENGA
ADDRESSING REVIEW
PH #: 740-6800
FAX #: 623-5411


TO:

CITY PLANNING

FROM:

AUDREY FARENGA BY M. NOWAK, ADDRESSING REVIEW

SUBJECT:

DP13-0016/ ST. AUGUSTINE CATHOLIC HIGH SCHOOL

DATE:

MARCH 27, 2013



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.

All addresses will need to be displayed per Pima County Address Standards at the time of final inspection.




***The Pima County Addressing Section can use digital CAD drawing files when
submitted with your final plat Mylar. These CAD files can be submitted through Pima
County Addressing. The digital CAD drawing files expedite the addressing
and permitting processes when we are able to insert this digital data into the County's
Geographic Information System. Your support is greatly appreciated.***
02/27/2013 GLENN HICKS COT NON-DSD PARKS & RECREATION Passed
02/27/2013 ED ABRIGO PIMA COUNTY ASSESSOR Passed
02/27/2013 PGEHLEN1 OTHER AGENCIES U. S. POST OFFICE Passed
02/27/2013 ROBERT YOUNG PIMA COUNTY PIMA CTY - DEV REVIEW Passed
02/27/2013 PGEHLEN1 UTILITIES CENTURYLINK Passed
02/27/2013 PGEHLEN1 UTILITIES EL PASO NATURAL GAS Passed
02/28/2013 KBROUIL1 COT NON-DSD FIRE Approv-Cond New building additions shall be subject to the 2012 IFC for fire flow and hydrant locations.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/28/2013 CPIERCE1 REJECT SHELF Completed