Permit Number: DP13-0003
Parcel: 13506163D

Review Status: Completed

Review Details: RESUB - SITE and/or GRADING

Permit Number - DP13-0003
Review Name: RESUB - SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/07/2013 STEVE SHIELDS ZONING REVIEW Approved
02/19/2013 RONALD BROWN HC SITE REVIEW Denied 1. Awkward transition from accessible parking space to accessible route.
a. Crossing in back of parking space hazardous
b. This is a marked crossing. Comply with ICC A117.1, sections 406.12, 13 and 14 and include detectable warnings.
c. Need direct access to accessible route, not a 90 degree turn in the PAAL.
d. Reference suggested sketch attached to drawing.
2. Access gate is not accessible. It is located off the accessible route.
3. Accessible route needs to be provided to door of accessible units. Reference suggested sketch attached to drawing.
4. Confirm with Zoning any changes in the widths of the PAAL
END OF REVIEW
02/21/2013 LOREN MAKUS ENGINEERING REVIEW Approved